Alarm Signal
The inverter alarm signal is active when a fault has 
occurred and it is in the Trip Mode (refer to the 
diagram at right). When the fault is cleared the 
alarm signal becomes inactive.
We must make a distinction between the alarm 
signal AL and the alarm relay contacts [AL0], 
[AL1] and [AL2]. The signal AL is a logic 
function, which you can assign to the open collec-
tor output terminals [11] or [12]. The relay is 
dedicated to the function AL, thus the labeling of its terminals. Use an open collector 
output (terminal [11] or [12]) for a low-current logic signal interface or to energize a 
small relay (50 mA maximum). Use the relay output to interface to higher voltage and 
current devices (10 mA minimum).
RUN
STOP
RESET
STOP
RESET
Run
Stop
Trip
Fault
Fault
Alarm signal active
Option
Code
Terminal 
Symbol
Function Name
Output 
State
Description
05
AL
Alarm Signal
ON
when an alarm signal has occurred and has not 
been cleared
OFF
when no alarm has occurred since the last 
clearing of alarm(s)
Valid for outputs:
11, 12
Required settings:
C_33
Notes:
When the alarm output is set to normally closed, a 
time delay of less than 2 seconds occurs until the 
contact is closed when the power is turned ON.
Terminals 11 and 12 are open collector outputs, so 
the electric specifications of [AL] are different 
from the contact output terminals [AL0], [AL1], 
[AL2].
When the inverter power supply is turned OFF, the 
alarm signal output is valid as long as the external 
control circuit has power.
This signal output has the delay time (300 ms 
nominal) from the fault alarm output.
The relay contact specifications are in 
. The contact diagrams for different condi-
tions are on the next page.
Example for terminal [11] or [12] (requires 
output configuration—see page 
):
RY
+
Example for terminals [AL0], [AL1], [AL2] 
(default output configuration shown—
see page 
):
See I/O specs 
on page 
12 11
L
H O OI
FM CM2
Inverter logic 
circuit board
Relay position 
shown is during 
normal running 
(no alarm).
AL0
AL2
AL1
AL
Inverter output 
terminal circuit
AL
Load
Power
supply