Emerson MODBUS 485 사용자 설명서
BACnet Communications - UPS Systems
333
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 109 Liebert NXL
™
- 60Hz, UL version (Model 40) - Glossary
Data Label
Data Description
Auto Restart In Progress
Auto restart is in progress
Auto Restart Inhibited - Ext
Auto restart inhibited due to an external signal
Auto Retransfer Time Remaining
Time remaining before an inverter overload or inverter fault can be cleared
and auto retransfer from the bypass to the inverter can take place
Automatic Restart Failed
Automatic restart failed
Backfeed Breaker Open
The backfeed breaker is in the open position
Backfeed Breaker
Backfeed breaker
Battery - External Monitor 1
External battery monitor 1 - battery maintenance required
Battery - External Monitor 2
External battery monitor 2 - battery maintenance required
Battery Amp-Hours Consumed This Discharge
Battery amp-hours withdrawn this discharge.
Battery Amp-Hours Consumed
Cumulative battery amp-hours withdrawn over the life of the battery
Battery Capacity Low
Battery capacity is low
Battery Cell Count - Lead Acid
Battery cell count - lead acid
Battery Cell Count-Nickel Cadmium
Battery cell count - nickel cadmium
Battery Charging Error
The battery is not charging properly
Battery Charging Inhibited
Battery charging is inhibited due to an external inhibit signal
Battery Charging Reduced-Extrnl
Using a reduced battery charging algorithm due to an external signal
Battery Circuit Breaker 1 Open
Battery circuit breaker 1 is open
Battery Circuit Breaker 2 Open
Battery circuit breaker 2 is open
Battery Circuit Breaker 3 Open
Battery circuit breaker 3 is open
Battery Circuit Breaker 4 Open
Battery circuit breaker 4 is open
Battery Circuit Breaker 5 Open
Battery circuit breaker 5 is open
Battery Circuit Breaker 6 Open
Battery circuit breaker 6 is open
Battery Circuit Breaker 7 Open
Battery circuit breaker 7 is open
Battery Circuit Breaker 8 Open
Battery circuit breaker 8 is open
Battery Commission Date
Date and time when battery placed into service
Battery Discharge Power
Instantaneous battery power while discharging
Battery Discharge Time
The time on battery operation for this discharge
Battery Discharging
The battery is discharging
Battery Equalize
The rectifier output voltage is increased to equalize the battery voltage
level.
Battery Ground Fault
Battery system ground fault amperage exceeds the threshold
Battery Last Discharge Date
The date and time of the last battery discharge
Battery Low Shutdown
Battery disconnect due to end-of-discharge.
Battery Low
The calculated battery time remaining has reached the low battery
threshold
Battery Over Temperature
A battery temperature sensor is reporting a value above a threshold
Battery Percentage Charge
The percentage of battery charge
Battery Self Test
Battery self test is in progress
Battery Temperature for Cabinet
The battery temperature for a cabinet
Battery Temperature Imbalance
Excessive temperature differences between battery sensors detected
Battery Temperature Sensor Fault
A battery temperature sensor fault has been detected
Battery Test Failed
Battery test failed
Battery Test Inhibited
Automatic (scheduled) battery tests are inhibited