Configuration 
3-2 
HP Uninterruptible Power System R1500 XR Models User Guide 
 
2.  Press and hold the Configure button (1) for three seconds. When the Configure button is 
released, the front panel configuration parameters flash in unison and the Configure 
Mode On LED (2) illuminates solid green. 
1
2
 
Figure 3-2:  Placing the UPS in Configure mode  
Configuration Parameters 
In Configure mode, the front panel LED display changes function to allow UPS monitoring. 
The LED control buttons allow modification of the UPS configuration parameters. The 
configuration parameters are defined in Table 3-1. Available voltage settings per model are 
listed in Table 3-2. 
 
Table 3-1:  Configuration Parameters 
Parameter (LED) 
Parameter Name 
Explanation (when illuminated) 
General Alarm 
(
100 Nom* 
Nominal utility voltage level is selected to 100 VAC.  
On Battery 
(
110/220 Nom 
Nominal utility voltage level is selected to 110/220 VAC. 
Bad Battery/Low 
Battery 
(
120/230 Nom 
Nominal utility voltage level is selected to 120/230 VAC. 
Site Wiring Fault 
Indicator 
(
127/240 Nom 
Nominal utility voltage level is selected to 127/240 VAC. 
Utility LED 
(
Site Wiring  
Fault Indicator 
Audible alarm is enabled if ground is missing, or if line 
and neutral connections are reversed.  
*The 200/208 parameter is printed on the front panel for future enhancement purposes.