Battery Maintenance 
4-2 
HP Uninterruptible Power System R1500 XR Models User Guide 
Determining When to Replace Batteries 
When the Bad Battery/Low Battery LED (1) illuminates red, batteries may need to be 
replaced within 30 to 60 days.  
 
100%
25%
1
1
 
Figure 4-1.  Bad Battery/Low Battery LED 
To check a battery alarm, initiate a UPS battery self-test to verify that battery replacement is 
required. If the Bad Battery/Low Battery LED (1) remains red, replace the batteries as soon 
as possible. 
 
NOTE:  Depending on usage and environmental conditions, the batteries should last three to six years.
For more information on initiating a self-test, refer to the section, “Initiating a Self-Test,” in 
Chapter 2. 
Obtaining New Batteries 
New batteries may be required within 30 to 60 days when the Bad Battery/Low Battery LED 
illuminates red. Obtain spare batteries for the UPS when this occurs. 
HP supplies spare battery packs for this UPS. The UPS spare battery kit part number is 
240789-001
.
 
 
 
CAUTION:  Because of the short shelf life of the battery, avoid storing a battery spare as a 
backup. Do not maintain an onsite inventory of spare batteries unless a procedure to keep 
these batteries charged while in storage is implemented.