Delta Electronics DOP-A/AE/AS 연결 가이드

다운로드
페이지 137
Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
 
1-14  
Revision January, 2008, Doc. Name: 2007PDD23000007 
AllenBradley MicroLogix PLC 
A. HMI factory setting 
Baud rate: 19200, 8, None, 1. 
PLC station number: 1. 
Control area/status area: B3:0/B3:10. 
B. Definition of controller Read/Write address 
Registers 
Read/Write Range 
Bit No. 
Register Type 
Format 
Word No. 
Low Byte 
High Byte 
File No. 
Output File 
O:n 
n: 0 ~ 3 
N/A 
Input File 
I:n 
n: 0 ~ 3 
N/A 
Status File 
S2:n 
n: 0 ~ 65 
N/A 
Bit File 
B3:n 
n: 0 ~ 255 
N/A 
Timer Flag 
T4:n 
n: 0 ~ 255 
N/A 
Timer Preset Value 
T4:n.PRE 
n: 0 ~ 255 
N/A 
Timer Accumulator Value 
T4:n.ACC 
n: 0 ~ 255 
N/A 
Counter Flag 
C5:n 
n: 0 ~ 255 
N/A 
Counter Preset Value 
C5:n.PRE 
n: 0 ~ 255 
N/A 
Counter Accumulator Value 
C5:n.ACC 
n: 0 ~ 255 
N/A 
Control File 
R6:n 
n: 0 ~ 255 
N/A 
Control Size of Bit Array 
R6:n.LEN 
n: 0 ~ 255 
N/A 
Control Reserved File 
R6:n.POS 
n: 0 ~ 255 
N/A 
Integer File 
N7:n 
n: 0 ~ 255 
N/A 
¾
  Bit No : Low byte is not used, so the value is 0. High byte stores file number. 
¾
  Data Size : Word. 
¾
  T4, C5 and R6 only read 1 Word once. 
¾
  If reading multiple Words once, the communication speed of PLC will be slow. 
NOTE
  
1)  After last communication data has been memorized by PLC (PLC will send 0x10 0x05 consecutively), 
communication may fail. At this time, power off and power up HMI or power off and power up PLC once.