Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series 
Revision January, 2008, Doc. Name: 2007PDD23000007 
 
 
1-17 
AllenBradley SLC5 PLC 
A. HMI factory setting 
Baud rate: 19200, 8, None, 1. 
PLC station number: 1. 
Control area/status area: B3:0/B3:10. 
NOTE
  
1)  Error Check uses CRC (Cyclical Redundancy Check). 
B. Definition of controller Read/Write address 
Registers 
Read/Write Range 
Word No. 
Bit No. 
Low Byte
High Byte 
Register Type 
Format 
Element No.
 
Slot or File No. 
Output File 
O:n 
O:s.n 
n: 0 ~ 30 
N/A 
Slot No. s = 0 
s: 0 ~ 255 
File No. = 0 
Input File 
I:n 
I:s.n 
n: 0 ~ 30 
N/A 
Slot No. s = 0 
s: 0 ~ 255 
File No. = 1 
Status File 
S2:n 
n: 0 ~ 255 
N/A 
File No. = 2 
Bit File 
Bf:n 
n: 0 ~ 255 
N/A 
f: 10 ~ 255 
If f is ignored, file no. will be 
default setting 3. 
Timer Flag 
Tf:n 
n: 0 ~ 255 
N/A 
f: 10 ~ 255 
If f is ignored, file no. will be 
default setting 4. 
Timer Preset Value 
Tf:n.PRE 
n: 0 ~ 255 
N/A 
f: 10 ~ 255 
If f is ignored, file no. will be 
default setting 4. 
Timer Accumulator Value 
Tf:n.ACC 
n: 0 ~ 255 
N/A 
f: 10 ~ 255 
If f is ignored, file no. will be 
default setting 4. 
Counter Flag 
Cf:n 
n: 0 ~ 255 
N/A 
f: 10 ~ 255 
If f is ignored, file no. will be 
default setting 5. 
Counter Preset Value 
Cf:n.PRE 
n: 0 ~ 255 
N/A 
f: 10 ~ 255 
If f is ignored, file no. will be 
default setting 5.