Keyence KV/KZ Series 
A. HMI factory settings 
Baud rate: 9600, 8, EVEN, 1 (RS-232). 
Controller station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) 
communication is allowed.) 
Control area/status area: DM-0 / DM-10. 
NOTE
 
1)  Please notice that no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication 
is allowed. 
2)  Only 1 Bit or 1 Word can be transferred for each communication. (Communication speed is slow.) 
B. Definition of controller Read/Write address 
Registers 
Read/Write Range 
Register Type 
Format 
Word No. 
Bit No. 
Data Length 
Timer T-nnn 
nnn: 
199 
N/A 
Word 
Counter C-nnn 
nnn: 
199 
N/A 
Word 
High-speed Counter 
CTH-n 
n: 
0 ~ 1 
N/A 
Word 
High-speed Counter 
Comparator 
CTC-n n: 
N/A 
Word 
Data Memory 
DM-nnnn 
nnnn: 0 ~ 1999 
N/A 
Word 
Temporary Data Memory 
TM-nn 
nn: 
0 ~ 31 
N/A 
Word 
Timer Preset Value 
PT-nnn 
nnn: 
0 ~ 199 
N/A 
Word 
Counter Preset Value 
PC-nnn 
nnn: 
0 ~ 199 
N/A 
Word 
CTC Preset Value 
PCTC-n 
n: 
0 ~ 3 
N/A 
Word 
Contacts 
Read/Write Range 
Contact type 
Format 
Word No. 
Bit No. 
Relay 
R-nnnbb 
nnn: 0 ~ 69 
bb: 
00 ~ 15 
Timer T-nnn 
N/A  nnn: 0 
199 
Counter C-nnn 
N/A 
nnn: 0 
199 
High-speed counter  
comparator 
CTC-n N/A 
n: