Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
 
1-52  
Revision January, 2008, Doc. Name: 2007PDD23000007 
Lenze LECOM-A/B Protocol 
A. HMI factory settings 
Baud rate: 9600, 7, EVEN, 1 (Baudrate: 1200/2400/4800/9600/19200). 
Controller station number: 1 (1~99). 
Control area/status area: None / None. 
NOTE
  
1)  Please pay close attention to each pin definition of cable connectors. 
2)  Ensure not to use the general RS-232 5-pin cable. This is because if pin 2, 3, 5, 7, 8 are all connected to 
the drive, the drive can not recognize the communication signal and can not identify what kind of 
communication it is.  
3)  For more detailed information of pin definition of cable connectors, please refer to the  C. Connections 
(Connector Pinouts) of Lenze LECOM-A/B Protocol controller. 
4)  Ensure the HMI communication data format (The communication data written into the drive) is correct. 
The Word “m” in the following table is used to specify the HMI communication data format. 
5)  Ensure the HMI display data format (Property table/Setting value...etc.) is correct. 
6)  When using broadcast function, please check if device is available. This is because the broadcast 
function can be activated only when the user chooses “write only” device for broadcast station number 
(only choose setting value/setting constant (button) and then the broadcast function can be used). If 
choosing other devices, the system will ask you to read back the drive setting value, so please ensure to 
choose the correct device. If choosing the incorrect devices, a “Controller Station Number Error…” fault 
message will display on HMI screen. 
7)  Support 82XX frequency inverters and 93XX servo inverters. 
B. Definition of controller Read/Write address 
Registers (n, m, y are in decimal) 
Read/Write Range 
Word No. 
Bit No. 
 
LowByte 
HighByte 
Register Type 
Format 
 
 
subcode 
Data Length 
CWn 
n: 1 ~ 10000 
N/A 
N/A 
Word 
Parameter without subcode
CWn.m 
n: 1 ~ 10000 
m: 0 ~ 23 
N/A 
Word 
Parameter with subcode 
CWn/y 
n: 1 ~ 10000 
N/A 
y:1 ~ 255 
Word 
 
CWn/y.m 
n: 1 ~ 10000 
m: 0 ~ 23 
y:1 ~ 255 
Word