Delta Electronics DOP-A/AE/AS 연결 가이드

다운로드
페이지 137
Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
 
1-78  
Revision January, 2008, Doc. Name: 2007PDD23000007 
Mitsubishi A2A/A2AS/A2USH A1SH/A3N/A2ASH (CPU-S1) CPU Port 
A. HMI factory settings 
Baud rate: 9600, 8, ODD, 1. 
Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) 
communication is allowed.) 
Control area/status area: D0 / D10. 
NOTE
 
1)  This driver supports all Mitsubishi A series CPU port. Mitsubishi A series CPU port can be divided into 
the following five categories according the used CPU code (used during communication): 
y
 
A0J2… 
y
 
A1N… 
y
 
A1S ( / A2S / A2N …) 
y
 
A3N ( / A1SH / A2SH …) 
y
 
A2A ( / A2AS / A2USH …) 
Delta HMI can support A2USH CPU port (same as A2A, A2AS CPU port.) and A1SH CPU port (same as 
A3N, A2ASH CPU port.). 
2)  L and M: The communication address of L is the same as communication address of M. 
3)  PX and X: 
In Mitsubishi A2A PLC, the communication address of PX and X are the same. 
In other Mitsubishi A series PLCs, X is from odd address and PX is from even address. That is one place 
where PX and X differ. 
4)  X, Y, B, M, SM, L, F, PX ----(Word), 
X, Y, B, M, SM, L, F, PX ----(Bit), 
When PLC station number is set to 255, only the value of even addresses will be read/written. 
When PLC station number is set to other number (not 255), all value of all addresses will be read/written. 
5)  R address: R address will be different according to the size of File Register responded from PLC. 
For example, A2USH: 
1K: 3800 ~ 4000H 
 
2K: 3000 ~ 4000H 
 
3K: 2800 ~ 4000H 
 
4K: 2000 ~ 4000H 
 
5K: 4000 ~ 6800H(cy) 
 
6K: 4000 ~ 7000H(cy) 
File Register: PLC must be started correctly or the read / write value will be incorrect.