NOTE
When used for the load less than rated
In the case of the load current less than 
rated, malfunction may result from the 
residual voltage across the both ends of 
the load even if the solid state relay is 
turned off.
Use a dummy resistor as a 
countermeasure.
The total of the current through the 
resistor and the load current must exceed 
the min. rated load current.
In case the dummy resistor is not used, 
keep in mind that the residual voltage 
becomes as follows:
Example:
For the inductive load by the 5 mA load 
current and the 200 V AC load voltage, 
the load impedance becomes 40 kW and 
Ve/V = 16% is estimated from the below 
graph.
Accordingly, the 32 V voltage remains 
across the both ends of the load when 
the solid state relay is turned off.
• Characteristics of residual voltage 
vs. load impedance
16
1
Load power source
Input power source
5
8
+
Load
R
0
(Dummy resistor)
( + )
( – )
0
20
40
20
40
60
100,%
80
100
60
80
100
Ve
Ve
V
V
SSR
1
2
Load
×
f =  60 Hz
Ve: Residual voltage
V: Power voltage
Power  factor: 1
(resistive  load)
Power  factor: 0.4
(inductive load)
Load impedance, k
Ω