INSTALLATION & MOUNTING
Installation Instructions:
1. If IP-EWST adaptor is not on the same LAN 
or network segment as the PC master 
station, ensure that the IP-EWST has been 
pre-programmed with the proper TCP/IP 
connection settings prior to physical adaptor 
installation.  See TalkMaster™ installation 
manual (included on CD with IP-EWST).
2. Set the personality jumper based upon your 
chosen sub station. IE-JA and IF-DA subs 
will work in “2W” mode. Any standard LE-
series sub (remove E/- jumper) or 4Ω ~ 20Ω 
speaker will work in “ST” mode.
3. Wire the sub station to the proper screw 
terminals on the IP-EWST, and connect to 
the network using the standard RJ-45 jack.  
Wiring from the sub station to the IP-EWST 
should be jacketed multi-conductor with 
overall shield.  Connect the included power 
supply to 2.1mm power jack (unless using IP-
EWST-POE)
2W
ST
2W
ST
Personality
Switch Settings
IE-JA/IF-DA
Sub stations
2W
ST
LE-Series
Sub stations
Mounting Instructions:
1. Ensure that proper sub station and network connections have been 
made prior to closing the IP-EWST chassis.
NOTE:  Once unit is mounted, the chassis cannot be opened to 
modify sub station wiring and internal settings. 
2. Mount the IP-EWST adaptor in a controlled area or in an enclosure 
suitable to the installation environment.  The stock IP-EWST chassis 
is not vandal resistant or weather resistant.  Mounting holes are 
located on the top center and bottom center of the back chassis.
Mounting hole
Mounting hole
Pg. 2
IE-JA / IFDA Sub stations
2-Conductor connection to 
IE-JA / IF-DA sub stations
Relay Output
for Door/Gate
N/C
Com
N/O
LE-Series Sub station or Speaker
3-Conductor connection to 
LE-series sub station
Relay Output
for Door/Gate
N/C
Com
N/O
E
1
-
Standard 
Speaker*
N/O push button
* When using a standard speaker, connect to E and 1 termination points.  
Wiring should be jacketed 3-conductor.
Wire distance from IP-EWST  to LE series sub:
22AWG = 650 feet,  18AWG = 1600 feet
*
* Wiring to sub station should be jacketed 2-conductor.
Wire distance from IP-EWST to IE/IF sub: 
22AWG = 500 feet,   18AWG = 1180 feet