Avaya 555-233-116 사용자 설명서

다운로드
페이지 246
1145B power supply
Issue 4   October 2002
33
555-233-116
Mountings
The back-up battery mounts on a top plate. The power supply and distribution 
units mount on a bottom plate. The plates are normally wall-mounted.
Installing the wall mounting
See 
.
1. Locate one plate directly below the other with the raised letters right side 
up. Be sure that the AC power cord can reach the electrical outlet from the 
bottom plate. The power cord is about 7.5 ft. (2 m) long.
NOTE:
Up to 4 power supplies can draw current from one 110- or 230-VAC, 
20- or 15-A feeder. Use only unswitched receptacles that are not 
shared with other equipment.
2. Secure the wall mounting plates to a 3/4-in. (2-cm) plywood mounting 
board using the four 1/2-in. #10 wood screws supplied with the plates.
3. Snap the 1145B power supply onto the bottom wall-mounting plate (no 
tools are needed).
4. Connect an insulated 17-AWG #12 (1.2-mm) ground wire (or better) 
between the ground lug on the power-supply frame  and an approved 
ground.
The frame ground screw is located next to the AC receptacle, to the left of 
the unit.
5. Write the unit number and connectivity information on the front label, next 
to the LEDs.