Chapter 2 - Field Panel Web Server System Administration 
Loading the User Interface 
16 
Siemens Industry, Inc. 
 
125-3584T
 
 
Loading the User Interface 
Be sure that the FPWeb license is enabled for each field panel. 
Recommended Method: Loading or Upgrading the User Interface via 
Human-Machine Interface (HMI) 
To load or upgrade the User Interface file via HMI (recommended method): 
  Copy the UIUpgrade folder and its contents from Vantage Web site onto the root of 
a USB memory device (such as a thumb drive). Do not change the folder or file 
structure.  
NOTE: The files within the UIUpgrade folder include wsroot/fpweb.swf as well as 
language (.mo) files and other support files.  
1.  Insert the USB memory device into the USB port of the field panel. 
NOTE: Due to USB memory device manufacturer, size, and contents, the time to 
detect the device will vary from several seconds to one or more minutes. You may 
verify that the device is attached by using the HMI commands S/H/F/F/L to list the 
available drives on the Field Panel, and confirm that Drive B is listed. 
2.  Use the HMI Uiupgrade function 
(System/Hardware/Ethernet/Webserver/Uiupgrade). When prompted, type Y for 
Yes, and press ENTER. 
  The User Interface and support files will be copied from the USB memory 
device in the field panel’s B:\ drive to the field panel’s internal flash drive (IFD) 
and to the field panel’s A:\ drive. 
Alternate Method: Loading or Upgrading the User Interface via File 
Transfer Protocol (FTP) 
There are many user-friendly FTP tools publicly available that can be used for 
transferring files between your computer and the field panel. 
Telnet must be enabled in order to use FTP. Remember to disable Telnet on the field 
panel when you are done using the Telnet and FTP services. For information on 
enabling Telnet, see 
Troubleshooting
 
Telnet must be enabled in order to use FTP. Remember to disable Telnet on the field 
panel when you are done using the Telnet and FTP services. For information on 
enabling Telnet, see the TALON Controllers User's Manual (588-580). 
To load or upgrade the User Interface file via FTP (alternate method; HMI method is 
recommended): 
  Use FTP to copy the UIUpgrade folder and its contents from Vantage Web site or 
your computer to the root of Drive A on the field panel.  
After the transfer, the contents of Drive A should look similar to the following folder 
structure: 
  Do one of the following: