5 - 3
MELSEC-A
5   PRELIMINARY INFORMATION
5.2 Programming Precautions
5.2.1 About bank changing of the A series master module
When using the R2, the master station's automatic update buffer or
transmission/reception buffer is used.
With the A Series master module (AJ61BT11/A1SJ61BT11), the automatic update
buffer and transmission/reception buffer are divided with banks. When accessing these
buffers, the bank must be changed.
POINT
When using dedicated commands (RITO, RIFR, RIRD, RIWT, RISEND,
RIRCV), the bank is changed with the dedicated commands, and does not need
to be changed by the user.
After changing to bank 1 or bank 2 and then reading or writing, return to bank 0.
The information such as RX, RY, RWw or RWr will not be updated unless the
bank is changed to bank 0.
A Series master module buffer memory (AJ61BT11/A1SJ61BT11)
Bank 0
Bank 1
Bank 2
Intelligent device 
station automatic
update buffer
Parameter, status 
information, etc.
Intelligent device 
station transmission
/reception buffer
 FFF
H
M
 
FFF
H
M
 
FFF
H
M
  0
H
M
 
 
0
H
M
 
 
0
H
M
Q/QnA Series master module buffer memory
(AJ61QBT11/A1SJ61QBT11/QJ61BT11/QJ61BT11N)
Intelligent device 
station automatic 
update buffer
Parameter, status
information, etc.
Intelligent device 
station transmission
/reception buffer
 FFF
H
M
1000
H
M
1FFF
H
M
2000
H
M
2FFF
H
M
  0
H
M
(1)   Changing the bank
The bank can be changed by turning the master module's Y(n+1)C, Y(n+1)D ON
and OFF.
n indicates the master module's head input/output No.
Y (n+1) C
Y (n+1) D
Details
OFF
OFF
Change to bank 0
ON
OFF
Change to bank 1
OFF
ON
Change to bank 2