Avaya S8100 사용자 설명서

다운로드
페이지 408
1 Install and cable a G600 cabinet
Check AC power and ground for G600
76
S8100 Installation and Upgrades
November 2003
Figure 10: Single-cabinet G600 grounding
Figure notes
1
10 AWG (#25) (6 mm
2
) wire to 
coupled bonding conductor (CBC).
2
6 AWG (#40) (16 mm
2
) ground wire from 
single-point ground block to the approved 
building ground.
1
2
cadpgnd1 LJK 102500