DNP3 telecontrol protocol
20
DNP3 telecontrol protocol
Widely distributed outstations (RTUs) can be controlled and 
monitored with the DNP3 telecontrol protocol via serial or 
Ethernet TCP/IP communication links by means of the tele-
control center in SIMATIC PCS 7. The control center integrated 
with SIMATIC PCS 7 TeleControl into the operator system of 
the process control system is the master during telecontrol 
communication. 
The slaves are represented by the outstations. SIMATIC 
S7-300/S7-300F and S7-400/S7-400F/S7-400H/S7-400FH 
controllers as well as third-party RTUs can be used as out-
stations.
Further hardware and software components round off the 
range of products:
• TIM communication modules
• TCP/IP  converters 
– serial and MD modem modules
• GSM/GPRS  components
• TCP/IP routers and switches
• SCALANCE S612 and S613 security modules
• Dedicated-line accessories
• Cables
• Engineering package for configuration of DNP3 data 
objects, stations, networks and connections as well as 
for diagnostics 
In order to implement the telecontrol networks, the basic 
topologies of point-to-point, multi-point, star and ring can be 
configured using classic or also TCP/IP-based media, and com-
bined flexibly independent of the infrastructural conditions.
DNP3 - example of classic dedicated network (star + multi-point topologies)
Classic WAN media
• Dedicated line via modem, e.g. SINAUT MD2
• Private wireless networks
• Analog telephone network
• Digital ISDN network 
• Mobile radio network GSM
RS 485
MD2
MD2
· · ·
· · ·
MD2
G_PCS7_XX_00267
MD2
MD2
MD2
Ethernet
MD2
Control center
SIMATIC PCS 7 TeleControl
DNP3 master
Dedicated network 
with star topology
Range without repeaters (example) 
with conductor cross-section 0.8 mm
- 1 200 bit/s 
max. 33 km
- 2 400 bit/s 
max. 27 km
- 19 200 bit/s 
max. 11 km
Star + 
multi-point
TIM 3V-IE 
DNP3 (slave)
TIM 3V-IE 
DNP3 (slave)
TCP/IP to serial 
converter
TIM 4R-IE 
DNP3 (slave)
TIM 4R-IE 
DNP3 (slave)
RTU S7-300
RTU S7-300
RTU S7-400H
RTU S7-400
© Siemens AG 2011