Pre-Installation 
2-2 
Copyright © 2005-2006 Eaton Corporation.  All Rights Reserved. 
IPN 997-00012-41D    December 2006 
 
 
Warnings 
This section contains important warnings relating to: 
• 
AC Inputs 
• 
Equipment Classification 
• 
Batteries (if applicable) 
• 
DC Outputs 
• 
Rectifiers 
• 
Location and Environment 
• 
Servicing 
• 
EMC Compliance 
 
 
AC Inputs 
 
• 
Desktop Versions:  
Pluggable Type A: Except for 120V input, if APS3-06X power systems are fitted with 
three rectifiers, then only two AC power cords may be connected to one building 
branch circuit.  The third AC power cord must be connected to a separate building 
branch circuit.  Failure to do so voids all safety approvals. 
• 
The maximum earth leakage current of each Access Power Rectifier is 1.5 mA.  Ensure 
that any upstream Residual Current Devices (RCDs) are appropriately rated. 
• 
The AC power cords (supplying the power system) must be suitably rated for the 
environment and AC power distribution system.  In addition, these AC power cords 
must be approved and installed to comply with local wiring regulations. 
• 
The earth conductor of each AC power cord must have a minimum cross sectional 
area of 1 mm
2
 (0.00155 in
2
). 
• 
The maximum length of each AC power cord should not exceed 3m (10 feet), unless 
local wiring regulations permit otherwise. 
• 
Ensure that the AC supply is disconnected from those fused AC power sockets before 
checking or replacing their respective fuses. 
• 
Each socket, K1 to K3 (APS3), and K1 to K6 (APS6), contain two fuses, FS1 and FS2. 
CAUTION: DOUBLE-POLE / NEUTRAL FUSING 
• 
Use only 15 A, 250 VAC, 6.3 x 32 mm, fast-acting fuses of the same type (Bussman 
ABC-15 or Littelfuse 314-015 Type 3AB) for continued protection against risk of fire. 
 
 
Equipment Classification 
 
• 
Data Power Solutions are classified as “Class 1” equipment that must be provided 
with an earth connected to the “Protective Earthing Conductor” in the building 
wiring.  The earth conductor of each AC power cord must be connected to the 
“Protective Earthing Conductor” in the building wiring. 
• 
APS3-06X (desktop versions) are classed as “Pluggable equipment Type A” and 
intended for use as “Desktop units”. All other units, APS3-05X and APS6-05X are 
“Pluggable Equipment Type B” or for “Permanently connection” in host equipment.