43
A.0500.551 – IM-TGMAG/02.00 EN (02/2008)
Symptom
Cause
Remedy
Pump leak
O-rings, sealing rings or gasket damaged 
or not correctly assembled
41 • Check condition of O-rings and assemble them 
correctly or replace them
• Check condition and clean/repair sealing faces
• Replace gasket under top cover or safety relief 
valve and/or sealing rings under plugs
Note! If symptoms persist, the pump must be taken out of service immediately. Contact your distributor.
3.20.1  Instructions for re-using and disposal
3.20.1.1  Re-use
Re-use or putting the pump out of service should only be undertaken after complete draining and 
cleaning of the internal parts. 
Note! When doing so, observe adequate safety regulations and take environmental  
protection measures.  
Liquids should be drained and following local safety regualtions the correct personal equipment 
should be used.
3.20.1.2  Disposal
Disposal of the pump should only be done after it has been completely drained. Proceed according 
to local regulations.
Where applicable please disassemble the product and recycle the parts’ material.
3.21  Maintenance instructions
3.21.1  General
This chapter only describes operations that can be performed on-site for normal maintenance. 
For maintenance and repair requiring a workshop contact your distributor.
•  Insufficient, wrong and/or irregular maintenance can lead to malfunctions in the pump, high  
repair costs and long-term inoperability. Therefore, you should carefully follow the guidelines 
given in this chapter.
 
During maintenance operations on the pump due to inspections, preventive maintenance or 
removal from the installation, always follow the prescribed   procedures.
 
Non-compliance with these instructions or warnings may be dangerous for the user and/or  
seriously damage the pump/pump unit.
•  Maintenance operations should be performed by qualified personnel only. Always wear the
required safety clothing, providing protection against high temperatures and harmful and/or  
corrosive fluids. Make sure that the personnel read the entire instruction manual and, in  
particular, indicate those sections concerning the work at hand.
•  SPX Process Equipment is not responsible for accidents and damage caused by non- 
compliance with the guidelines.
•  Personnel who carry a cardiac pacemaker should not be allowed to work on a pump equipped
with magnetic coupling!. The magnetic field is sufficiently strong to affect the proper operation  
of a pacemaker, so keep a safe distance of at least 3 m.
•  Do not come close (not less than 1 m) to the magnetic coupling with subjects equippid with
magnetic data carrier such as cheque cards, computer disks, watches etc. to avoid damage  
and/or loss of information.
3.21.2  Preparation
3.21.2.1  Surroundings (on site)
Because certain parts have very small tolerances and/or are vulnerable, a clean work environment 
must be created during on site maintenance. Particularly remove metallic chips or any dirt which 
could be attracted by the components of the magnetic coupling.