Installation
11
513220
Exhaust System
For best drying results, recommended maximum 
length of exhaust system is shown in Table 1.
To prevent backdraft when dryer is not in operation, 
outer end of exhaust pipe must have a weather hood 
with hinged dampers (obtain locally).
NOTE:  Weather hood should be installed at least 
12 inches (30.5 cm) above the ground. Larger 
clearances may be necessary for installations where 
heavy snowfall can occur.
Table 1 
NOTE: The maximum length of a 4 in. (10.2 cm) 
diameter flexible metal duct must not exceed 
7.87 ft. (2.4 m), as required to meet UL2158, clause 
7.3.2.A.
Number of 
90° Elbows
Weather Hood Type
Recommended
Use Only for Short Run Installations
Maximum length of 4 in. (10.2 cm) diameter rigid metal duct.
0
65 feet (19.8 m)
55 feet (16.8 m)
1
55 feet (16.8 m)
47 feet (14.3 m)
2
47 feet (14.3 m)
41 feet (12.5 m)
3
36 feet (11.0 m)
30 feet (9.1 m)
4
28 feet (8.5 m)
22 feet (6.7 m)
NOTE: Deduct 6 feet (1.8 m) for each additional elbow.
4 in.
(10.2 cm)
4 in.
(10.2 cm)
D673I
D802I
2-1/2 in.
(6.35 cm)