   GEM-P1664 Installation Instructions 
L
 NAPCO Security Systems 
WI1424A  1/06 
 
Page 8
 
Smoke Detectors, 4-Wire: 
1. ESL 445AT, 445C, 445CT, 445CR, 445CRT 
2. Hochiki America SLG-12 with YBC-RL4-RA Base 
3. System Sensor 2312/24T; 1412; 1412TH; 2412TH 
Subtract total smoke-detector alarm current from available standby current. 
Note:  Any normally-open devices that do not require power from the control panel, such as pull stations and 
thermostats may be used if acceptable to the Authority having Jurisdiction. 
Smoke detectors & Summar
of U
L
 Requirements 
UL Compatible Smoke Detectors (Providing UL Recognition or Listing) 
Manufacturer 
4-Wire 
Smoke Detector 
2-Wire 
Smoke Detector * 
Smoke Detector 
Base 
Napco 
FW-4 
FW-2 
 
Sentrol 
 
 
 
 
 
 
 
 
System 
Sensor 
 
 
 
 
 
449AT 
449C 
449CRT 
449CST 
449CSRT 
449CSRH 
449CSST 
449CLT 
449CSLT 
449CTE 
741U 
742U 
712U 
722U 
732U 
711U 
721U 
721UT 
731U 
1112 
2112 
2112T 
2112TSRB 
2100 
2100T 
1100 
701U 
702U 
702RE 
702RU 
Note: * Voltage Rating: 8.5-13.3 VDC, Maximum Number of Detectors: 10 
SUMMARY OF UL REQUIREMENTS 
Residential 
Recognized Limited-Energy Cable for initiating, indicating and supplementary circuits. 
Initiating loops supervised if longer than 3 feet 
FT2200 End-of-Line Relay for Fire (if using 4-wire smoke detectors) 
Minimum alarm timeout of 5 minutes 
Maximum exit time: 60 seconds 
Maximum entry time: 45 seconds 
Do not program “Swinger Shutdown”, “Force Arming”, “Selective Bypass” or “50 ms Loop Response” 
“Abort Delay” may not exceed 45 seconds 
Program “Disable Callback Download” 
Automatic dialer may not dial a police station number that has not been dedicated for such service 
System must be tested at least weekly under AC/battery and Battery-Only conditions 
Replace the rechargeable battery at least every 5 years 
If the battery is heavily discharged, replace it or have it tested by a qualified technician 
For silent panic, connect only to UL-listed holdup devices 
All zones must be programmed for “Priority” 
Do not program any zones for “Keyswitch Arming” 
System must be serviced at least once every year 
Residential Fire and Combination Residential Fire & Burglary must program “Residential Fire” 
Keypad Expansion (EZM) Zones are not to be used as fire zones 
Keypad Auxiliary is not to be selected 
The GEM-K Series Keypads must have the indicators printed on the face label (Fire, Police and Auxiliary) covered by a 
supplied label if not in use.