Honeywell R4795A Manual Do Utilizador

Página de 16
7
60-2285—7
R4795A
INSTALLATION
Fig. 6—Flame detector wiring.
M8686
BLUE
WHITE
F
G
C7027, C7035, OR C7044
ULTRAVIOLET FLAME DETECTOR
BLUE
YELLOW
BLACK
BLACK
F
G
C7012 ULTRAVIOLET DETECTOR
1
G
F
X
X
X
X
X
X
FLAME ROD
G
F
X
X
PHOTOCELL
1
C7027, C7035, AND C7044 FLAME DETECTOR LEADS ARE COLOR 
CODED BLUE AND WHITE.  THE BLUE LEAD MUST BE CONNECTED 
TO THE F TERMINAL AND THE WHITE LEAD MUST BE CONNECTED 
TO THE G TERMINAL.  THIS CIRCUIT IS DC AND THE UV SENSING 
TUBE IS POLARITY SENSITIVE.  REVERSING THE LEADS EVEN
 MOMENTARILY CAN DAMAGE OR DESTROY THE UV TUBE.
POWER
SUPPLY
Fig. 7—Alarm terminal connections.
Mounting R4795 On Subbase
Make sure that the power supply is disconnected.
Loosen the thumbscrew and remove the cover (see Fig. 8).
Position the R4795 over the Q270 Subbase. Start all ten
mounting screws and tighten uniformly. These screws com-
plete electrical circuits (terminal 1 excepted) and hold the
R4795 to the subbase.
L1 
(HOT)
L2
1
1
2
2
IF A LINE VOLTAGE ALARM IS USED, THE R4795 MUST BE 
MOUNTED IN A SUITABLE ENCLOSURE.
POWER SUPPLY MUST MATCH THE ELECTRICAL RATINGS OF THE 
ALARM. PROVIDE DISCONNECT MEANS AND OVERLOAD 
PROTECTION AS REQUIRED.
LINE OR
LOW VOLTAGE
ALARM
ALARM TERMINALS (OPTIONAL)
N.C.
N.O.
COM
M8687
R4795
ALARM 
POWER
SUPPLY
CAUTION
Do not overtighten the mounting screws because
damage to the circuit board can result. Maximum
recommended torque is 10 lb-in. (1.13 N•m).
Replace cover and securely tighten thumbscrew.
Fig. 8—R4795 and Q270 Subbase.
TERMINAL 
BLOCKS
PURGE TIMER
AMPLIFIER
COVER
THUMBSCREW
SAFETY SWITCH
RESET BUTTON
IN COVER
CAPTIVE MOUNTING 
SCREWS (10)
Q270 
SUBBASE
M8688