Roberts Gorden CRV-B-4 Manual Do Utilizador

Página de 40
SECTION 6: R
ADIANT
 T
UBE
 
AND
 T
AILPIPE
  
17
4. Select pump model series for total system flow 
units: 
EP-100: up to 66 flow units 
EP-200: up to 110 flow units 
EP-300: up to 224 flow units
5. See Page 14, Table 2 for altitudes greater than 
2000'.
6. For each branch, add the length of radiant tube 
after each heater:
Repeat this calculation for each branch in the 
system.
7. Divide the total radiant tube length in the branch 
by the number of burners in the branch to get 
the average radiant length per burner.
Repeat this calculation for each branch in the 
system.
8. Using the average radiant length per burner 
(Calculated in Step 7See Page 17, Table 4 to 
select the allowable tailpipe lengths per flow 
unit.
Table 4: Allowable Tailpipe Lengths
*Minimum tailpipe lengths can only be used if radiant tube length is recommended or greater.
Burner
Radiant Tube Length 
After Each Burner
1
+
2
+
3
+
4
+
5
+
6
+
Total Radiant Tube 
Length in Branch = 
Average Radiant 
Length Per Burner = 
 
 Burner Model
B-2
B-4
B-6
B-8
B-9
B-10
B-12/B-12A
Radiant Tube Length (average distance between burners)
 
 
 
 
 
 
 
Minimum (ft)
10
12.5
20
20
20
30
35
Recommended (ft)
15
20
25
30
30
40
50
Maximum (ft)
20
25
35
45
50
60
70
Tailpipe length per flow unit
 
 
 
 
 
 
 
Minimum (ft)*
1.2
1.2
1.2
1.2
1.2
1.2
1.2
Recommended (ft)
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Maximum (ft)
2.5
2.5
2.5
2.5
2.5
2.5
2.5
Maximum (ft) for EP-100 only
1.7
1.7
1.7
1.7
1.7
1.7
1.7