Roberts Gorden 10081601NA Rev H 12/11 Manual Do Utilizador

Página de 70
SECTION 2: S
PECIFICATIONS
17 of 62
Enclosure: 
NEMA 4 gasketed aluminum LB
housing, ½" threaded connection
NEMA 4 Enclosure for Indoor Sensor 
(P/N 10081510)
Description:
NEMA 4 Enclosure is sold separately
as an option. The indoor sensor is
field mounted inside the NEMA 4
enclosure. Temperature thermistor
and LCD temperature display will not
operate properly inside the 
enclosure. LCD display feature should 
be disabled and use of the NEMA 4
sensor enclosure will require the use
of an outdoor sensor (P/N 10081501)
in the space to monitor zone 
temperature.
Dimensions:  W x H x D 
(in): 6.3 x 3.6 x 1.8 
(cm): 16.0 x 9.1 x 4.6
Construction: Polycarbonate enclosure with clear
front cover, 4 screw cover closure. 16
gauge galvanized subpanel.
Protection 
Rating:
NEMA 4, 4X
Flammability 
Rating:
UL-94-5V
2.6 Line Reactor 480 V / 4 A Output
Construction: Fabricated in accordance with UL
specifications from code gauge steel,
NEMA 1.
Dimensions:
W x H x D 
(in): 10 x 8 x 8 
(cm): 25 x 20 x 20
Rated 
Current:
4 A
Volts:
480 V / 3 Ø
Line Reactor 480 V / 4 A Input
Construction: Fabricated in accordance with UL
specifications from code gauge steel,
NEMA 1.
Dimensions:
W x H x D 
(in): 10 x 8 x 8 
(cm): 25 x 20 x 20
Rated 
Current:
4 A
Volts:
480 V / 3 Ø
Voltage Surge Suppressor 277 / 480 V
Construction: NEMA 2X Enclosure
Volts:
277 / 480 V
Frequency:
50/60 Hz
Wiring Size:
#12 AWG Standard Wire