Roberts Gorden 10081601NA Rev H 12/11 Manual Do Utilizador

Página de 70
ROBERTS GORDON
®
 ULTRAVAC™ C
ONTROLLER
 I
NSTALLATION
 M
ANUAL
32 of 62
5.3 TCP/IP Communication Module
For remote on-site viewing of system status and    
settings of any controller, use the TCP/IP communi-
cation module to connect the controllers to a Local 
Area Network (LAN) via Ethernet cable. Any         
computer on the LAN that has ULTRAVAC™ soft-
ware installed can be used to communicate with the 
controllers.
The module must be mounted inside the 
ULTRAVAC™ central controller (controller #1) 
enclosure next to the control board.   The power (5V) 
for the module will come from the ULTRAVAC™ 
control board. The module will communicate to the 
controller via regular phone wire from the RJ11 jack 
on the module to the RS-232 direct connect port on 
the control board. The module will relay the data
from the controller to computers on the LAN via 
Ethernet cable plugged into the RJ45 jack on the 
module. A setup procedure must be performed on 
the module upon installation to create its IP address 
on the LAN. The setup instructions can be found in 
the ROBERTS GORDON
®
 Software Manual (P/N 
10081600NA).
For TCP/IP communication module wiring details, 
see 
If multiple ULTRAVAC™ controllers are being used, the 
additional controllers communicate to controller #1 
through RS-485 communication wiring arranged 
in-series from one controller to the next. 
Section 5.5. This allows multiple controllers to be 
controlled from a PC through a single communication 
package at the central controller.
FIGURE 17: TCP/IP Communication Module Mounting