Roberts Gorden 10081601NA Rev H 12/11 Manual Do Utilizador

Página de 70
ROBERTS GORDON
®
 ULTRAVAC™ C
ONTROLLER
 I
NSTALLATION
 M
ANUAL
36 of 62
5.5.1 Repeater
If the RS-485 communications wire length is above 4000' (1219 m), a repeater must be used to extend the 
signal. The repeater can also be used to install in different methods:
• To extend communications beyond the standard 4000' (1219 m) limitation. 
• To add parallel branches of ROBERTS GORDON
®
 ULTRAVAC™ controller communications bus wiring.
NOTE: The maximum number of ROBERTS GORDON
®
 ULTRAVAC™ Controllers that can be installed is 
242.
FIGURE 21: Repeater External Wiring  
Description
Part Number
Repeater
URVRP