Roberts Gorden 10081601NA Rev H 12/11 Manual Do Utilizador

Página de 70
SECTION 7: V
ARIABLE
 F
REQUENCY
 D
RIVE
 P
ROGRAMMING
43 of 62
the password must be entered in order to access the 
parameters again.
7.2 Altering VFD Parameters
Using the procedure described 
7.1.1 through Section 7.1.5, alter the following parame-
ters:
Parameter 
Number
Parameter 
Name
Factory 
Default
New 
Setting
P01
Line Voltage
01
01 
P03
Start Method
01
05
P05
Standard 
Speed 
Source
01
(03) (0-10) Vdc
(04) (4-20) mA
P44
Password
225
Any #
000-999
P45
Speed at 
Minimum 
Signal
0.0Hz
Frequency 
Setting noted 
P46
Speed at 
Maximum 
Signal
60.0Hz
Frequency 
Setting noted