SECTION 12: USER INSTRUCTIONS
12.1 User Instructions
The DualAir
®
 units are fully automatic and operate 
from the external controls fitted on site. 
The only user controls at the heater are the:
Burner lockout reset button:
...................................See Page 26, Section 12.3.3
Limit thermostat reset:
.................................... See Page 25, Section 12.3.1
Second limit thermostat reset button:
...................................See Page 25, Section 12.3.2
12.2 Heater Operation
When the heater has been switched on by the 
remote controls installed, the main burner will 
automatically turn on.
The burner control box will control the ignition of the 
flame.
All heaters require a constant gas and electricity 
supply which must not be interrupted during the 
normal operation of this heater.
12.2.1 Warning Lights
The DualAir
®
 unit has three warning lights;
GREEN = Heater ON, burner attempting to fire
RED = Burner LOCKOUT, see Section 12.3.3.
AMBER = Dirty Filter, replace filter, air flow is 
dropping to an unacceptably low value.
Figure 14: Heater Operating Sequence
12.3 Common User Controls
12.3.1 Combination Fan/Limit Thermostat
The Combination Fan/Limit Thermostat is located 
inside the access door at the top of the heater. See 
Page 38, Section 16.3
This control ensures the heater does not blow cold 
air in the normal heating cycle and protects the heat 
exchanger against overheating.
Figure 15: Fan/Limit Thermostat
12.3.2 Secondary Limit Thermostat
WARNING
Electrical Shock Hazard
Disconnect electrical power before servicing.
Failure to follow these instructions can result in
death or electrical shock.
ON
RUN ON
CLOSE
DOWN
THERMOSTAT
CALL FOR
HEAT
BURNER
RUN
FAN
ON
ON
White fan button
Pull out for normal operation.
Press in for constant fan.
Red limit reset button
(Press to reset)
The combination fan/limit thermostat is preset 
during commissioning.
See Page 7, Section 4.3
NOTE: To reset, the heat exchanger must be cool.
If the air flow is reduced due to power failure the 
limit thermostat will cause the burner to lockout.
Description
Part Number
Combination Fan/Limit Thermostat
K017A
Press to reset
These are hand reset devices to give further 
protection against fan failure.
NOTE: To reset, the heat exchanger must be cool.
Description
Part Number
Secondary Limit Thermostat
90412100