SECTION 11: VENTING AND FRESH AIR SUPPLY
11.1 Type C
12
 , C
32
 & C
62
 Appliance
Room Sealed
The heaters are designed to be installed as room sealed 
appliances. The flue and air intake are run as separate 
pipes to the special concentric wall or roof terminal. The 
wire mesh inside the fresh air adapter on the heater must 
be removed prior to installation. See Page 51, Figure 31.
11.2 Type B
22
 Appliance
The flue must be fitted with a low resistance terminal. See 
Page 51, Figure 31
.
11.3 Flue Installation
The fan outlet may discharge vertically or horizontally. 
Connection should be made using 100 mm minimum 
diameter Aluminium or Stainless Steel flue material to 
National Standard and must be adapted to insert into the 
100 mm flue adapter. Both fresh air supply and flue duct 
shall not exceed 10,000 mm. HE15 and HE20 flue must 
be insulated if longer than 5,000 mm. HE25 flue must be 
insulated if longer than 8,000 mm. For each 90° bend, 
subtract 1,000 mm from the maximum flue length. The 
flue must be self supporting. Suitable terminals must be 
fitted for horizontal and vertical flue.
In order to locate fans that are not IP54 protected away 
from the wet environment, a 100 mm diameter extension 
tube between the heat exchanger end and fan must be 
installed. This length must be subtracted from the 
maximum flue length. 
Fans
Horizontal
Vertical
83 BWLG
190 mm x 75 mm (hole)
150 mm dia.
90 BWLG
190 mm x 75 mm (hole)
150 mm dia.
11.4 Ventilation Requirements
Detailed recommendations for air supply are given in the 
relevant National Standards. There must be an adequate 
supply of air for both combustion and general ventilation. 
Air vents should have negligible resistance. Do not locate 
air vents where they can be easily blocked or flooded, or 
adjacent to any flues or extraction systems carrying 
flammable vapour.
11.5 Fresh Air Supply
The burner is equipped with a fresh air adapter which has 
a silicone gasket incorporated. This adapter accepts 
tubes with 100 mm outside diameter.
WARNING
Carbon Monoxide Hazard
Multiburner systems are not approved for 
unvented use and must be vented outdoors.
Unitary heaters installed unvented must be 
interlocked with sufficient building exhaust.
Heaters must be installed according to the 
installation manual.
Failure to follow these instructions can result 
in death or injury.
WARNING
Cut/Pinch Hazard
Wear protective gear during installation, 
operation and service.
Edges are sharp.
Failure to follow these instructions can result 
in injury.
Fresh Air Adapter
Fresh Air
Supply Duct
100 mm OD