Carrier 48SX024-060 Manual Do Utilizador

Página de 52
REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 36 (914)
Compressor access
. . . . . . . . . . . . . . . . . . . . . 36 (914)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 14 (356)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Flue panel
. . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side . . . . . . . . . . . . . . . . 42 (1067)
Unit and ungrounded surfaces, control box side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side . . . . . . . . . . . . . . . . . . 42 (1067)
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
UNIT HEIGHT
(in./mm)
lb
kg
A
B
C
D
E
48SS180040
208/230-1-60
272
123
81/37
62/28
76/35
53/24
24.1/613
48SS024040
208/230-1-60
303
138
97/44
43/20
123/56
40/18
24.1/613
48SS024060
208/230-1-60
315
143
100/45
46/21
126/57
43/20
24.1/613
48SS030040
208/230-1-60, 208/230-3-60
320
145
100/45
47/21
126/57
47/21
24.1/613
48SS030060/080
208/230-1-60, 208/230-3-60
332
149
103/46
50/22
129/58
50/23
24.1/613
48SS036060/080
208/230-1-60, 208/230-3-60, 460-3-60
336
153
86/39
76/35
111/50
63/29
24.1/613
48SS036100/120
208/230-1-60, 208/230-3-60, 460-3-60
348
158
89/40
79/36
114/52
66/30
24.1/613
48SS042060/080
208/230-1-60, 208/230-3-60, 460-3-60
375
170
95/43
86/39
119/54
75/34
28.1/714
48SS042100/120
208/230-1-60, 208/230-3-60, 460-3-60
387
176
98/45
89/40
122/55
78/35
28.1/714
UNIT
F
in./mm
G
in./mm
CENTER OF GRAVITY in./mm
X
Y
Z
48SS018040
16
9
16
/420.7
18
15
16
/481.0
25.07/637
20.59/523
10.85/276
48SS024040
27.07/688
23.35/593
48SS024060
26.98/685
23.27/591
48SS030040
26.71/678
23.46/596
48SS030060/080
27.15/689
22.36/568
48SS036060/080
27.50/698
22.48/571
48SS036100/120
27.40/696
22.44/570
48SS042060/080
20
9
16
/522.3
22
15
16
/582.6
27.01/686
22.44/570
12.7/321
48SS042100/120
26.94/684
22.44/570
LEGEND
CG
— Center of Gravity
COND — Condenser
LV
— Low Voltage
MAT’L
— Material
NEC
— National Electrical Code
REQ’D — Required
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
fan discharge.
2. Adequate clearance around air openings into combustion chamber must
be provided.
Fig. 2 — 48SS018-042 Without Base Rail, Unit Dimensions