  CAUTION:  Use  only  new, 
black  iron  or  steel  pipe.  Inter-
nally-tinned copper tubing may 
be used in certain areas. Check 
your  local  codes.  Use  pipe  of 
large enough diameter to allow 
proper gas volume to heater. If 
pipe is too small, undue loss of 
volume will occur.
Typical Inlet Pipe Diameters
CRN18(T) and CRP16(T) - 3/8" or greater
CRN30(T) and CRP26(T) - 1/2" or greater
CRT30NT and CRT26PT - 1/2" or greater
Installation must include equipment shutoff valve, 
union and plugged 1/8" NPT tap. Locate NPT tap 
within reach for test gauge hook up. NPT tap must 
be upstream from heater (see Figure 15).
IMPORTANT:
 Install an equipment shutoff valve 
in an accessible location. The equipment shutoff 
valve is for turning on or shutting off the gas to 
the appliance.
Apply  pipe  joint  sealant  lightly  to  male  NPT 
threads. This  will  prevent  excess  sealant  from 
going into pipe. Excess sealant in pipe could result 
in clogged heater valves.
  WARNING:  Use  pipe  joint 
sealant that is resistant to liquid 
petroleum (LP) gas.
Install sediment trap in supply line as shown in 
Figure 15. Locate sediment trap where it is within 
reach for cleaning. Locate sediment trap where 
trapped matter is not likely to freeze. A sediment 
trap traps moisture and contaminants. This keeps 
them from going into heater controls. If sediment 
trap is not installed or is installed wrong, heater 
may not run properly.
IMPORTANT:
 Hold the pressure regulator with 
wrench when connecting it to gas piping and/or 
fittings. Do not over tighten pipe connection to 
regulator. The regulator body could be damaged.
Tee    Pipe    Cap
Joint   Nipple
INSTALLATION
Continued
Tee Joint
Reducer 
Bushing to 
1/8" NPT
1/8" NPT 
Plug Tap
*  A CSA design-certified equipment shutoff valve 
with 1/8" NPT tap is an acceptable alternative to 
test gauge connection. Purchase the optional CSA 
design-certified equipment shutoff valve from your 
dealer. See Accessories, page 23.
Figure 15 - Gas Connection
Pressure 
Regulator
T
es
t G
au
ge
 C
on
ne
ct
io
n*
Heater 
Cabinet
Sediment Trap
Equipment 
Shutoff 
Valve *
3" 
Min.
Natural Gas
From Gas 
Meter (7" W.C. 
to 10.5" W.C. 
Pressure)
Propane/LP
From External 
Regulator 
(11" W.C. to 14" 
W.C. Pressure)
Regulator 
Bracket
Ground 
Joint 
Union
3/8" NPT 
Pipe 
Nipple
CHECKING GAS CONNECTIONS
 WARNING: Test all gas piping 
and  connections,  internal  and 
external to unit, for leaks after 
installing or servicing. Correct 
all leaks at once.
  WARNING:  Never  use  an 
open flame to check for a leak. 
Apply a noncorrosive leak detec-
tion fluid to all joints. Bubbles 
forming show a leak. Correct all 
leaks at once.
  CAUTION:  For  propane/LP 
gas, make sure external regula-
tor has been installed between 
propane/LP supply and heater. 
See guidelines under 
Connect-
ing to Gas Supply, page 11.