DO NOT reverse the inlet and outlet (cold and hot water) connections on the 
unit. This would cause the Rinnai Water Heater to operate dangerously or not 
at all.
0
Rinnai America
FF  Models
I N S TA L L E R ’ S  I N S TA L L AT I O N  I N S T R U C T I O N S
Water Piping Notes
1)  A  manual  water  control  valve  must  be  placed  upon  the  water  inlet  connection  to  the  Rinnai 
Water  Heater  before  it  is  connected  to  the  water  line.    Unions  may  be  used  on  both  the  hot/
cold  water  supply  lines,  for  the  future  servicing  or  disconnection  of  the  unit.
2)  All  soldering  materials  and  piping  must  be  compatible  with  potable  water. 
3)  Purge  the  water  line  to  remove  from  it  all  debris  and  air.  Debris  will  damage  the  Rinnai 
Water  Heaters. 
4)  There  is  a  wire  mesh  strainer  on  the  Rinnai  Water  Heater’s  inlet  to  discourage  the 
introduction  of  debris  to  the  unit.  It  will  need  to  be  cleaned  periodically.    DO  NOT  operate 
unit  without  filter  in  place.  Clean  this  filter  before  leaving  the  job  site.
I N S TA L L E R ’ S  I N S TA L L AT I O N  I N S T R U C T I O N S
Pressure Relief Valve
1)  ANSI code calls for the addition of an approved pressure relief valve to all water heating systems. 
2)  The  pressure  relief  valve  must  meet  the  following  criteria: The  relief  valve  must  comply  with  the 
standard  for  Relief  Valves  and Automatic  Gas  Shutoff  Devices  for  Hot  Water  Supply  Systems ANSI 
Z21.  22  and/or  the  standard  CAN1-4.4 Temperature,  Pressure, Temperature  and  Pressure  Relief 
Valves  and  Vacuum  Relief  Valves.   This  relief  valve  must  be  rated  up  to  150  PSI  of  pressure. 
3)  The  relief  valve  should  be  added  to  the  hot  water  outlet  line  per  manufacturer's  instructions. 
DO  NOT  place  any  other  type  valve  or  shut  off  device  between  the  relief  valve  and  the  hot 
water  heater. 
4)  The discharge from the pressure relief valve should be piped to the ground or into a drain system to 
prevent exposure or possible burn hazards to humans or other plant or animal life. Water discharged 
from the relief valve could cause severe burns instantly, scalds and/or death. 
5)  Do not plug the relief valve and do not install any reducing fittings or other restrictions in the relief 
line. The relief line should allow for complete drainage of the valve and the line. 
6)  If  a  relief  valve  discharges  periodically,  this  may  be  due  to  thermal  expansion  in  a  closed 
water  supply  system.    Contact  the  water  supplier  or  local  plumbing  inspector  on  how  to 
correct  this  situation.    Do  not  plug  the  relief  valve.
7)  Pressure  relief  valve  must  be  manually  operated  once  a  year  to  check  for  correct  operation.
 
Caution:    See  Item  4  before  manually  operating  relief  valve. 
8)  Should  overheating  occur  or  the  gas  supply  fail  to  shut  off,  turn  off  the  manual  gas  valve  on 
the  Rinnai.