Roberts Gorden DAT75 Manual Do Utilizador

Página de 52
D
UAL
A
IR
®
 H
EATING
 
AND
 
COOLING
 U
NITS
 I
NSTALLATION
 O
PERATION
 
AND
 S
ERVICE
 M
ANUAL
30 
SECTION 14: CONVERSION BETWEEN GASES
14.1 General
Conversion between gasses will require a change of 
burner injectors and the gas valve re-commissioning 
to the new conditions.
14.2 Burner Conversion
Conversion of the burner assembly from one gas to 
the other is the same for all types of heaters.
1. Remove the burner compartment cover as 
2. Remove the connection between the gas valve 
outlet and the manifold. See Page 36, Section 
16.1
 for gas valve removal.
3. Remove the manifold from the burner assembly 
by removing the screws at the top and bottom. 
See Page 37, Section 16.2.1
4. Remove the main burner injectors.
5. Replace with the injectors for the new gas 
ensuring a gas tight seal.
6. Refit all components in reverse order.
14.3 Gas Valves
All gas valves used on the DualAir
®
 units have 
pressure regulators that may be set to operate on 
natural gas or LPG.
Conversion is carried out by re-setting the burner 
pressure to the value in the data table during 
commissioningSee Page 7, Section 4.3.
Ensure that the gas inlet pressure to the heater is 
correct for the new gas, and that the gas supply has 
been purged of the old gas.