2. PROPER CHIMNEY HEIGHT: 
The chimney shall terminate at least 3 feet above the highest point where it passes through the roof of a 
building and at least 2 feet higher than any portion of a building within a horizontal distance of 10 feet. 
(See Fig. 2a). 
                           
 
Fig. 2: Proper chimney termination height for pitched roofs 
 
If the chimney penetrates a roof more than 10 feet from a ridge, wall or parapet, a minimum of 3 feet 
above roof or exit point must be maintained.  See Figure 2b. 
 
If the roof is flat rather than the normal residential pitched roof, refer to Figure 3 for proper clearances. 
 
Fig. 3: Proper chimney termination height for flat roofs 
 
3. PROPER VENT CONNECTOR PIPE/CHIMNEY CONNECTION: 
The vent connector pipe should extend only to (and not beyond) the inside wall of the chimney (See Fig. 
4). A thimble should be used to connect the vent connector pipe to the chimney so that the vent 
connector pipe may be readily removed in case of inspection or replacement.  
 
 
Fig. 4: Proper insertion of the vent connector in the chimney.