Thermo Products OH8FA119D60B Manual Do Utilizador

Página de 78
 
 36 
 
 
 
A.  Inputs 
 
Power supplies 
Line voltage is applied between the “S1” and “N1” quick connect terminals.  24 VAC Class II 
Transformer secondary voltage supplied to X and C 
 
Limit switch 
 
 
The 120 VAC optically isolated limit switch input is connected on pin P2-1 & 9.  Refer to the Heat 
Mode section for the control operation. 
 
Thermostat  call for heat “W” 
24 VAC thermostat input. A call for heat is recognized when the thermostat connects “W” to “R”. This 
input has an indicator  LED that will light when the control receives a call for heat. Refer to the Heat 
Mode section for the control operation. 
 
Thermostat call for cool, “Y” 
24 VAC thermostat input. A call for cooling is recognized when the thermostat connects “Y” to “R”. This 
input has an indicator LED that will light when the control receives a call for cooling. Refer to the Cool 
Mode section for the control operation. 
 
Thermostat call for dehumidification “DEHUM” 
24 VAC thermostat input. A call for dehumidification is recognized when the humidistat connects 
“DEHUM” to “R”. This input has an indicator that will light when the control receives a call for 
dehumidification. Refer to the Cool Mode section for the control operation. 
 
Thermostat call for fan “G” 
 
24 VAC thermostat input. A call for fan is recognized when the thermostat connects “G” to “R”. This 
input has an indicator LED in that will light when the control receives a call for fan. Refer to the Fan 
Mode section for the control operation. 
 
B.  Outputs 
 
PSC Control 
The control shall control a five-speed indoor blower motor. Rating shall be 10 FLA, 30 LRA @ 120 
VAC. Connections are made via 0.250 x 0.032” male quick connect terminals labeled “HEAT”, 
“COOL”, and “LOW”. “HEAT” is energized when the heat speed blower is to run. “COOL” is energized 
when the Cool speed blower is to run. “LOW” is energized during a call for fan is received or a call for 
dehumidification is received. 
 
Oil Burner                        
 
 
 
Control 
The control provides dedicated contacts to operate the T-T input of an oil primary control. 
 
Rating shall be class 2 – 24 VAC pilot duty @ 24 VAC (<200mA). 
 
 
Power 
The switched 120 VAC power from the LIMIT switch passes through the board between Pins 1 & 2 
of connector P1. 
 
     
 
Compressor contactor 
The control provides switched 24VAC to operate a compressor contactor. Rating shall be class 2 – 24 
VAC pilot duty @ 24 VAC (<200mA).