Louisville Tin and Stove HEDV404 Manual Do Utilizador

Página de 22
REFERENCE LETTER TO 
DRAWING 
CANADIAN 
INSTALLATIONS¹ 
A = Clearance above grade,  
veranda, porch, deck, or 
balcony 
12 Inches (30 cm) 
B = Clearance to window or door 
that may be opened 
12 Inches (30 cm) 
C = Clearance to permanently 
closed window 
12 Inches (30 cm) 
D = Vertical clearance to 
ventilated soffit located above 
the terminal within a horizontal 
distance of 2 Feet (61 cm) from 
the center line of the terminal 
18 Inches (46 cm) 
E = Clearance to unventilated 
soffit 
18 Inches (46 cm) 
F = Clearance to outside corner 
12 Inches (30 cm) 
G = Clearance to inside corner 
12 Inches (30 cm) 
H = Clearance to each side of 
center line extended above 
meter/ regulator assembly 
3 Feet (91 cm) within a hei
15 Feet (4.5m) above the 
meter/regulator assembly 
I = Clearance to service regulator  
vent outlet 
3 Feet (91 cm) 
J = Clearance to nonmechanical 
air supply inlet to building or the 
combustion air inlet to any other  
appliance 
12 Inches (30 cm) 
K = Clearance to a mechanical 
air supply inlet 
6 Feet (1.83 m) 
L = Clearance above paved 
sidewalk  or paved driveway 
located on public property 
7 Feet (2.13m)  A vent shal
not terminate directly abo
a sidewalk or paved drivew
th t i l
t d b t
t
VENT TERMINAL CLEARANCES
Page 4
Vent Terminal
Air Supply Inlet
Area where terminal is not permitted