 Installation 
(for qualified installers only)
 
17 
© Travis Industries 
4090717 
100-01225_000 
 Horizontal Termination with Three 90° Elbows (all vertical) 
• 
If using a Snorkel Termination (14” or 36”) add the snorkel height to the vertical height (snorkel 
terminations are used primarily for basement installations). 
• 
The termination must fall within the shaded area shown in the chart.  Use the indicated restrictor 
position. 
5 feet (1.5m)
10' min (3m)
15 feet (4.5m)
21' max (6.4m)
0 feet
5 feet (1.5m)
0 feet
0 feet
5 feet (1.5m)
10' min (3m)
15 feet (4.5m)
Restrictor 
Position # 5
NOTE:
Restrictor positions are based 
upon lab tests.  The ideal restrictor 
position may vary slightly, 
especially when the termination is 
near a demarkation line.
Restrictor 
Position # 1
10 feet (3m)
15 feet (4.5m)
20 feet (6m)
24 ' max (7.3m)
0 feet
5 feet (1.5m)
10 feet (3m)
15 feet (4.5m)
20 feet (6m)
24 ' max (7.3m)
21' max (6.4m)
NOTE: 
Horizontal sections require a 1/4" (0.250mm)
rise every 12" (305mm) of travel.
This is a horizontal elbow -
NOT ALLOWED FOR THIS 
VENT CONFIGURATION
These are 
vertical elbows.