Sterling SDA 1000-5100 Manual Do Utilizador

Página de 61
Large Dehumidifying Dryers  
Mechanical Installation 
25 
After cooler 
Model
Water Flow 
( GPM )
AD600
10
AD850
10
AD1000
15
AD1250
15
AD1500
20
AD2000
25
AD2500
30
AD3000
35
High 
Temperature 
Gasket
Stainless Steel Cooler 
Housing
Cooling Coil
Cooling Coil 
Pipe Gasket
Cooling Coil 
Cover Plate
Mounting Brackets
High 
Temperature 
Gasket
Cooling Coil
Cooling Coil 
Pipe Gasket
Mounting 
Brackets
Stainless Steel 
Cooler Housing
Cooling Coil 
Cover Plate
After cooler 
Model 
Water Flow 
(GPM) 
600 10 
850 10 
1000 15 
1250 15 
1500 20 
2000 25 
2500 30 
3000 35 
 
3-6   Connecting Aftercooler/Precooler Cooling Water (Optional) 
Support both sides of the fitting when making the cooling water connections to prevent 
damage to the aftercooler coil. See Figure 9. 
Connect 85°F water to the inlet closest to the exiting air side of the aftercooler coil. This will 
cool the process air about 100°F and raise the water-out temperature about 10°F.  The table 
below lists available aftercooler models and their flow rates. 
Figure 9: Aftercooler Components & Flow Rates