INSTALLATION
VENTING ARRANGEMENTS 
HORIZONTAL TERMINATION (FLEX)
Regency
®
 Direct  Vent System 
These venting systems, in combination with the L900-1, have been tested and listed as a direct vent system by Warnock Hersey. The location of the 
termination cap must conform to the requirements in the Vent Terminal Locations diagram from the "Exterior Vent Termination Locations" section.
FPI Direct Vent (Flex) System Termination Kits include all the 
parts needed to install the L900-1 using a fl exible vent.
Notes: 
1)  Liner sections should be continuous without any joints 
or seams.
2)  Only Flex pipe purchased from FPI may be used for Flex 
installations.
3)  Horizontal vent must be supported every 3 feet.
4)  A wall thimble is mandatory for all horizontal terminations 
due to high temperatures.
 
FPI Kit # 
Length  Contains:
#946-615
4 Feet
1) 8” 
fl exible liner (Kit length)
2) 5” 
fl exible liner (Kit length)
3) spring 
spacers
4) thimble
5)  AstroCap termination cap
6) screws
7)  tube of Mill Pac
8) plated 
screws
9)  S.S. screws #8 x 1-1/2” drill point
10)  vinyl siding standoff
#946-618
6 Feet
#946-616
10 Feet