Heat & Glo LifeStyle 6000TRS-CE Manual Do Utilizador

Página de 45
Heat & Glo  •  6000TRS-CE  •  2049-900 Rev. Q  •  2/11
31
A tap is provided on the outlet side of the gas control for a 
test gauge connection to measure the manifold pressure. 
To measure inlet pressure, provisions must be made to 
attach a test gauge to  the tap immediately upstream of 
the gas supply connection to the fi replace.
The fi replace and its individual shut-off valve must be 
disconnected from the gas supply piping system during 
any pressure testing of the system at test pressures in 
excess of 60 mbar.
If the fi replace must be isolated from the gas supply 
piping system by closing an individual shut-off valve, it 
must be of the handle-less type.
Pressure requirements for Heat & Glo gas 
fi replaces are shown in the table below.
Step 7
Gas Pressure
Requirements
 
Natural Gas 
Propane
Butane
Natural Gas
(G20)
 (G31)
(G30)
(G25)
Inlet Pressure
20 mbar
37 or 50 mbar 30 or 50 mbar
25 mbar
Manifold Pressure
4-8.7 mbar
15.7-25 mbar
15.7-25 mbar
4-8.7 mbar
Gas Rate
.54 
m3
/
h
.24 
m3
/
h
.16 
m3
/
h
.54 
m3
/
h
Max. Input(NETCV)
10.0 kW
10.0 kW
9.5 kW
8.5 kW
Burner Injector
DMS 33
1.8 mm
DMS 51
DMS 33
Pilot Injector
51
30
30
51
Step 8
Wiring the
Fireplace
Optional Accessories
Optional remote control 
kits require that 230 VAC 
be wired to the factory in-
stalled junction box before 
the fi replace is permanently 
installed.
!
WARNING: DO NOT CONNECT 230 VAC 
TO THE GAS CONTROL VALVE OR THE 
APPLIANCE WILL MALFUNCTION AND THE 
VALVE WILL BE DESTROYED
.
NOTE: Electrical wiring must be installed by a 
competent electrician.
For Standing Pilot Ignition Wiring
Appliance Requirements
Wall Switch 
Position the wall switch in the desired position on a wall. Run a maximum of 780 
cm or less length of 0.102 cm diameter minimum wire and connect it to the fi replace 
ON/OFF switch pigtails.