STEP  4.  Assemble  the  desired  lengths  of  black 
pipe and elbows necessary to reach from 
the  appliance  adapter  up  through  the 
Round  Support  Box.  Insure  that  all  pipe 
and  elbow  connections  are  in  their  fully 
twist-locked position.
STEP  5.  Cut  hole  in  the  roof  centered  on  the 
small  hole  placed  in  the  roof  from  Step 
2.  The  hole  should  be  of  sufficient  size 
to  meet  minimum  requirements  for 
Clearance  to  Combustibles,  as  specified. 
Continue  to  assemble  lengths  of  pipe 
and elbows necessary to reach from the 
ceiling  support  box  up  through  the  roof 
line.  Galvanized  pipe  and  elbows  may 
be utilized in the attic, as well as above 
the  roof  line.  The  galvanized  finish  is 
desirable above the roof line, due to the 
higher corrosion resistance.
Initial Installation
QUALIFIED INSTALLERS ONLY
V
ERTICAL
 I
NSTALLATION
:
STEP 1. Check  the  instructions  for  required  clearances  (air  spaces)  to  combustibles  when  passing 
through ceilings, walls, roofs, enclosures, attic rafters, or other nearby combustible surfaces. Do 
not pack air spaces with insulation.
STEP 2. Set the gas appliance in the desired location. Drop a plumb bob down from the ceiling to the 
position of the appliance flue exit, and mark the location where the vent will penetrate the ceiling. 
Drill a small hole at this point. Next, drop a plumb bob from the roof to the hole previously drilled 
Figure 19: Wall Framing Hole for Vertical Installation. 
in the ceiling, mark the spot where the vent 
will  penetrate  the  roof.  Determine  if  ceiling 
joists,  roof  rafters,  or  other  framing  will 
obstruct the venting system. You may wish to 
relocate the appliance, or to offset, to avoid 
cutting load bearing members.
STEP 3. To install the Round Support Box/Wall Thimble 
in a flat ceiling, cut a 10 inch (25.4 cm) square 
hole in the ceiling, centered in the hole drilled 
in Step 2. Frame the hole as shown in Figure 
19.
Vertical
Vent Cap
Roof
Truss
Insulation
Insulation
Guard
Ceiling
Rafter
Support
Collar
Storm
Collar
Roof Flashing
15 feet (4.57m)
Maximum
Vertical
Venting
Interior Wall
Surface
Insulation
Minimum
Clearance to
Combustibles
Exterior
Wall Surface
If installed
on a carpeted
surfacea hearth
is required
Figure 20: Vertical Installation.