Enviro 50-1033 Manual Do Utilizador

Página de 48
12
Figure 9: 
Removing valve 
cap.
Maintenance And Service
the HI/LO knob by hand shown in Figure 9.
Figure 11: Flip 
valve screw.
b)  Insert a 
5
/
32
” or 4 mm Allen wrench into 
the hexagonal key-way of the screw (see 
Figure  10),  rotate  it  counter-clockwise 
until it is free and extract it.
c)  Check  that  the  screw  is  clean  and  if 
necessary remove dirt.
d)  Flip the screw (refer to Figure 11).
e)  Using  the  Allen  wrench  as  shown  in 
Figure  10,  rotate  the  screw  clockwise 
Figure 12: O-ring on valve screw.
Figure 10: Removing 
valve screw.
6. Convert the pilot injector:
a) Pull the pilot hood straight up to access 
the pilot injector. 
b) Using  a 
5
/
32
”  or  4  mm  Allen  key, 
remove the pilot injector.
c) Install the new pilot injector supplied 
with this conversion kit.  Simply screw 
the new injector inside the pilot hood 
using the Allen key, 
d) Reinstall the hood by placing the hood 
on the assembly, line up the key way, 
and snap into place.
7.  Convert the SIT gas valve:
a)  Remove the black protection cap from 
Figure 13. Ignitor 
assembly beside the 
burner.
until a torque of 9 inch lbs. WARNING! Do not over tighten the screw. It is 
recommended that you grip the wrench by the short side.
f)  Verify  that  if  the  conversion  is  from  NG  to  LPG,  the  screw  must  be  re-
assembled with the red o-ring visible (refer to Figure 12). If the conversion 
is from LPG to NG, the red o-ring of the screw must be not visible.
g)  Re-attach the black protection cap that was removed in step a (Figure 9).
8.  Reinstall the burner, brick panels, log set, embers, and glass door. Also refer 
to S
ECONDARY
 I
NSTALLATION
 - L
OG
 S
ET
 
AND
 E
MBERS
 I
NSTALLATION
. When re-installing the 
burner, ensure that the burner to pilot hood relationship is similar to what is 
shown in Figure 13. On some units you will need to pay special attention when 
installing the burner that the venturi adjustment rod is properly installed into 
the venturi adjustment piece welded to the burner venturi tube
9.  Reconnect the main gas line if it was disconnected and open the shut-off valve at the gas line to the 
unit.
10.  Use a small brush to apply a warm soapy water solution to all gas connections (use a half dish soap 
and half warm water). If a gas leak is present, bubbling will occur. Gas leaks can be repaired by 
using an approved pipe thread sealant or approved Teflon tape. NEVER USE AN OPEN FLAME WHEN 
TESTING FOR LEAKS.
11.  Reconnect the electrical power to the unit.
12.  Relight the main burner in both the “HI” and “LO” positions to verify proper burner ignition and 
operation  and  proper  flame  appearance.  Also  refer  to  S
ECONDARY
  I
NSTALLATION
  -  L
OG
  S
ET
 
AND
  E
MBERS
 
I
NSTALLATION
 for a flame appearance picture. 
13.  MAKE SURE that the conversion label is installed on or close to the rating label to signify that the 
unit has been converted to a different fuel type.