Enviro 50-1033 Manual Do Utilizador

Página de 48
1
2
3
4
5
���� ������� �����
���� ���������� �����
���� ������� �����
������ ���������� �����
1
2
3
4
5
Figure 22: Restrictor plate settings.
The ENVIRO WESTPORT has been designed with a built in restrictor 
plate. The restrictor is designed to enhance flame appearance when 
installing this unit with vertical chimneys as well as installations with 
longer  horizontal  vent  applications.  It  does  this  by  controlling  the 
amount of air moving through the vent pipe.
Figure 23 shows the vent restrictor position required, relative to the 
length of vent pipe.  Longer vertical vent lengths necessitate greater 
restriction; position 1 is open and position 5 is maximum restriction 
(refer to Figure 22). To avoid injury, it is best to make this adjustment 
when the fireplace is cool or use welder’s gloves or oven mitts.
19
V
ENT
 C
ONFIGURATIONS
 
AND
 R
ESTRICTOR
 S
ETTINGS
:
Figures 23 & 24 show the range of venting options, they show possible vent configurations if the unit is 
top vented (see Figure 23) or rear vented (see Figure 24), for vertical and horizontal terminations, any 
layout that remains within the shaded area is acceptable. Having the fewest number of elbows is ideal, 
as they tend to disrupt air movement. Using 45˚ elbows is preferable to using 90˚ elbows. Also, a shorter 
vent system will perform better than a longer one.
Initial Installation
QUALIFIED INSTALLERS ONLY
Figure 23. Possible Vent Configurations for Top Vented; 
Vertical and Horizontal Terminations.
To  access  vent  restrictor  remove  the  valve 
cover plate from the right rear corner of the 
unit by undoing the two fastening screws.
Loosen the 1⁄4” hex head screw and adjust to 
the correct setting.
Slide the hex head screw to the next setting 
and re-tighten the screw to secure in place.
The numbers in this chart represent the actual 
vent restrictor settings. Although the numbers 
do not appear on the unit use this as a guide 
to follow.
Wait  for  unit  to  warm  up  to  operating 
temperature  to  ensure  proper  and  clean 
burning unit.
Figure 24. Possible Vent Configurations for Rear 
Vented; Vertical and Horizontal Terminations.
Note: 0,0  in  Figures  23  &  24  represent 
the outlet of the flue collar elbow.