Ultimate Products SC Manual Do Utilizador

Página de 58
 
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com
  - 2 -
             
WARNING: Improper installation, 
adjustment, alteration, service or 
maintenance can cause property 
damager, injury, or death.  Read the 
installation, operating, and maintenance 
instructions thoroughly before installing or 
servicing this equipment. 
 
A. INSTALLATION INSTRUCTIONS 
 
A.1 
TECHNICAL DATA 
(a) General Information 
 
              Model & Heat Input 
 
Information all units: 
 
 
Gas Supply Connection:  ½-inch NPT Male 
 
Electrical Supply:  120V, 1 phase, 60Hz 
 
Current Rating:  1.2 AMP MAX (Burner-0.3/Fan – 
0.9) 
 
Ignition:  Electronic Program Start-up with 
Spark Ignition 
 
OPTIONS: 
1.  Modify combustion chamber air intake for fresh air duct. 
2.  Ultimate Products Black Bulb Thermostat. 
3.  Control Panel with multi-zone capabilities.  (Not A.G.A. Certified) 
4.  Individual Heater Vent to Exterior. 
 
Notes: 
A.  Heater is intended for heating non-residential indoor and outdoor spaces and 
should only be installed where flammable gases or vapors are not generally 
present. 
B.  Indoor heaters may be suspended either horizontal or at an angle, or may be wall 
mounted.  Outdoor heaters must be suspended horizontally.   SEE SECTION A.3 
FOR CLEARANCES.
 
C.  Installation shall conform with local building code requirements and with National 
Fuel code ANSI-Z223.1.A. (Latest Edition) and section 7.8A-3; Z223.1 (Latest 
Edition). 
D.  The unit shall be electrically grounded in accordance with National Electric Code 
ANSI/NFPA 70-1987. 
E.  The heater may be installed in aircraft hangars when conformation with 
ANSI/NFPA 409-1985 for Aircraft Hangars and in automotive garages when 
conforming with ANSI-NFPA 88A (Latest Edition) for Parking Structures and 
ANSI/NFPA 88B (Latest Edition) for Repair Garages. 
 
Insure that minimum clearance will be maintained to vehicles parked below 
the heater.