FMI MM63 Manual Do Utilizador

Página de 44
www.fmiproducts.com
125160-01A
7
pre-installation preparation
 WaRnInG: do not pack required air spaces 
with insulation or other materials.
Minimum/Maximum Chimney Height for  
Residential Installation
Minimum height of chimney, measured from base of 
fireplace to flue gas outlet of termination, is 14 feet 
for straight flue or 17 feet for a flue with one elbow 
set. Maximum distance between elbows is 6 feet. For 
systems with two elbow sets, minimum height is 22 
feet. Maximum height of any system is 40 feet. This 
measurement  includes  fireplace,  chimney  sections 
and  height  of  termination  assembly  at  level  of  the 
flue gas outle
t (see Figure 20, page 16).
FRaMInG
1. Frame opening for fireplace using dimensions shown 
in 
Figures 6 and 7
.
2. If fireplace is to be installed directly on carpeting, 
tile (other than ceramic) or any combustible material 
other than wood flooring, fireplace must be installed 
upon a metal extending full width and depth of fire-
place.
3. Set fireplace directly in front of this opening and 
slide unit back until nailing flanges touch side fram-
ing.
4. Check level of the fireplace and shim with sheet 
metal if necessary.
5. Before  securing  fireplace  to  prepared  framing, 
ember protector (provided) must be placed between 
hearth  extension  (not  supplied)  and  under  bottom 
front edge of fireplace to protect against glowing em-
bers falling through. If fireplace is to be installed on 
a raised platform, a Z-type ember protector (not sup-
plied) must be fabricated to fit your required platform 
height. Ember protector should extend under fireplace 
a minimum of 1 
1
/
2
". Ember protector should be made 
of galvanized sheet metal (26 gauge minimum to pre-
vent corrosion.
6. Using screws or nails, secure fireplace to framing 
through flanges located on sides of fireplace.
seleCTInG loCaTIon
To determine the safest and most efficient location 
for the fireplace, you must take into consideration the 
following guidelines:
1. The location must allow for proper clearances (see 
Figures 6 and 7
).
2. Consider a location where fireplace will not be af-
fected by drafts, air conditioning ducts, windows or 
doors.
3. A location that avoids cutting of joists or roof raf-
ters will make installation easier.
4. An  outside  air  kit  is  available  with  this  fireplace 
(see 
Optional Outside Air Kit on page 12
).
MInIMUM CleaRanCe To CoMBUsTIBles
The  distance  to  be  maintained  from  the  surfaces 
of the fireplace to combustibles must be observed. 
Below  is  a  list  of  the  most  common    combustible 
materials to name a few:
Drywall 
 
Wood Flooring 
Plywood
Sub-Flooring  
Wood Framing 
Mill Board
Particle Board 
Plywood Paneling
Maintain the following clearances:
Unit sides, rear, Dome sides, rear & top..........2" min. 
Combustible Floors (MM33,39,44,49)..............6"  min.   
Combustible Floors (MM63 only).....................8" min.
Combustible Sheathing above opening top..18" min. 
Sheathing or trim to opening sides...................8" min. 
Mantel above opening..........................
see Figure 5 
Opening to sidewall...............................................24" 
Hearth extension beyond front.............................20" 
Hearth extension beyond sides............................12" 
Insulation from firebox............................................2"
Figure 5: Mantel Clearances to Combustible 
Material