VENTING INSTALLATION 
INSTRUCTIONS
NOtICE:  Read  these  instructions  completely  before 
attempting installation.
These models are tested and approved for use with DESA (direct-
vent) pipe components and terminations as well as Simpson-Duravent 
direct-vent pipe components and terminations.
The venting system must terminate on the outside of the structure 
and can not be attached to a chimney or flue system serving a 
separate solid fuel or gas burning appliance. A direct-vent appli-
ance must have its own venting system. DO NOT common vent 
this appliance.
These models are approved to be vented either horizontally through 
an outside wall or vertically through a roof or chase enclosure using 
the following guidelines:
•  When venting system terminates horizontally on an outside 
wall, you must install a standoff if the termination cap is to be 
installed directly on a combustible finish such as vinyl, wood, 
stucco, etc.
•  Never run the vent downward as this may cause excessive tem-
peratures which could cause a fire.
•  Vent pipe air space clearances to combustibles are 1" on all sides 
except on the horizontal sections, which requires 2" clearance 
from the top of the pipe. Where the termination cap penetrates 
a combustible wall, 1" air space clearance is required.
•  Snorkel terminations are required when minimum clearance to 
grade cannot be met (see Figure 16 on page 11).
•  Have fireplace and selected vent components on hand to help 
determine the exact measurements when elbowing or offsetting. 
Always use wall firestops when penetrating walls and firestops 
when penetrating ceilings or attic spaces.
•  If using a venting configuration of only horizontal venting with 
no vertical run, a 1/4" rise for every 12" of run toward the ter-
mination is required.
  WARNING:  Read  all  instructions  completely  and 
thoroughly  before  attempting  installation.  Failure  to 
do so could result in serious injury, property damage 
or loss of life.
NOtICE: Failure to follow these instructions will void 
the warranty.
IMPORTANT
: Do not seal vent cap to pipe. Cap must be remov-
able for service.
INStALLAtION PRECAUtIONS
•  Wear gloves and safety glasses for protection
•  Use extreme caution when using ladders or when on roof tops
•  Be aware of electrical wiring locations in walls and ceilings
The following actions will void the warranty on your venting system:
•  Installation of any damaged venting component
•  Unauthorized modification of the venting system (Do not cut or 
alter vent components)
•  Installation of any component part not manufactured or approved 
by DESA
•  Installation other than as instructed by these instructions
 WARNING: this gas fireplace and vent assembly 
must  be  vented  directly  to  the  outside.  The  venting 
system must NEVER be attached to a chimney serving 
a separate solid fuel burning appliance. Each direct-
vent gas appliance must use a separate vent system. 
Do not use common vent systems.
 WARNING: Vent pipe air space clearances to com-
bustibles are 1" on all sides except on the horizontal 
sections, which require 2" clearances from the top of 
the pipe. Where the termination cap penetrates a com-
bustible wall, 1" air space clearance is required.
INSTALLATION PLANNING
There are two basic types of direct-vent installation:
•  Horizontal Termination
•  Vertical Termination
Horizontal Termination Installation
IMPORTANT:
 Horizontal square terminations require only inner 
portion of wall firestop. Horizontal installations using round ter-
mination require exterior portion of wall firestop available only in 
vent kit 01491 (see Figure 14, page 10).
1.  Set the fireplace in its desired location and determine the route 
your horizontal venting will take. Do not secure the fireplace 
until all venting has been installed. Some installations require 
sliding the fireplace in and out of position to make final venting 
connections. Figures 14 through 18 on pages 10 and 11 show 
different configurations for venting with horizontal termina-
tion that will help you decide which application best suits your 
installation. Check to see if wall studs or roof rafters are in the 
path of your desired venting route. If they are, you may want 
to adjust the location of the fireplace.