Code Requirements:
u
The electrical installation must conform to the most current version of the National
Electrical Code, NFPA  No. 70, and all applicable local and state codes.
u
National Electrical Code, article 680; Swimming Pools, Fountains, and Similar Installations, shall
apply.
u
National Electrical Code, article 440, Air-Conditioning and Refrigeration Equipment, shall apply.
Reference Equipment Data Plate:
u
All TropiCal heat pumps have their data plates located on the left, exterior, side panel.
Refer to equipment data plate for unit-specific electrical power and over-current protection
requirements.  Based on data plate information; size wiring, devices, and over-current
protection per applicable codes and standards.
u
See drawing below for data plate details specific to Electrical Installation Requirements. The
numbered areas represented below will contain the necessary information required in sizing
electrical service and over current protection devices.
MADE IN THE USA
PHASE
MAXIMUM TIME DELAY FUSE OR HVAC BREAKER
L.R.A.
FAN MOTOR Vac
REFRIGERANT: Factory charged R-22 Only
Tested to 500 psig High side/150 psig Low side
INDOOR/OUTDOOR USE
 
     
AQUA CAL, INC 
  A TEAM HORNER COMPANY 
    2737 24
TH
 STREET NORTH 
  ST. PETERSBURG, FL 33713
 
 FACTORY SERVICE 
          1-800-786-7751 
 
 
          ETL LISTED 
MANUFACTURING CODE
SERIAL NO.
BAR CODE
#1
#2
#3
#4
#5
#6
#7
#8
MINIMUM CIRCUIT AMPACITY
 HZ
ELEC. SERVICE:
Vac.~
COMPRESSOR Vac
R.L.A
 F.L.A.
  H.P.
oz/Kg