 Fault  Code 
Defect code 
Defect explanation 
Ed 
Evaporator de-frosting defect. 
AS 
Indoor ambient temperature sensor failure in heating, cooling, dry and auto 
mode. 
HS 
DAHT sensor failure in heating mode. 
LO 
Sensor disconnection malfunction in fan only mode 
HI 
Sensor short circuit malfunction in fan only mode 
 
6. COMPONENT OPERATION & TESTING 
 
WARNING: 
DISCONNECT THE POWER CORD FROM THE POWER PLUG BEFORE SERVICING OR 
TESTING. 
6.1 COMPRESSORS 
Compressors are single phase, 115 or 230/208 volt, depending on the model number. All 
compressor motors are permanent split capacitor type using only a running capacitor across 
the start and run terminal. 
All compressors are internally spring mounted and externally mounted on rubber isolators. 
 
COMPRESSOR WINDING TEST (See Figure 1) 
Remove compressor terminal box cover and disconnect   
wires from terminals. Using an ohmmeter, check   
continuity across the following: 
1. Terminal "C" and "S" - no continuity   
- open winding - replace compressor. 
2. Terminal "C" and "R" - no continuity   
- open winding - replace compressor. 
3. Terminal "R" and "S" - no continuity   
- open winding - replace compressor.                 Figure 1: Compressor winding test 
 
GROUND TEST 
Use an ohmmeter set on its highest scale. Touch   
one lead to the compressor body (clean point of   
contact as a good connection is a must) and the   
other probe in turn to each compressor terminal   
(see Figure 2.) If a reading is obtained, the   
compressor is grounded and must be replaced.               Figure 2: Typical ground test 
 