FAN PERFORMANCE 
 
CSV060B 
 
 
 
 
CSV096B 
 
 
 
 
CSV120B 
 
 
 
SUPPLY AIR BLOWER PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1600
645 0.29 733 0.36 814 0.43 888 0.50 958 0.57 1024 0.64 1087 0.72 1154 0.83 1211 0.91 1245 0.99
1800
708 0.40 788 0.48 863 0.55 933 0.63 999 0.71 1061 0.79 1121 0.87 1178 0.95 1233 1.04 1295 1.17
2000
763 0.52 837 0.61 907 0.69 973 0.77 1035 0.86 1095 0.95 1152 1.04 1207 1.13 1260 1.22 1311 1.31
2200
836 0.69 904 0.78 969 0.87 1030 0.97 1089 1.06 1145 1.15 1199 1.25 1252 1.35 1303 1.45
~
~
2400
898 0.88 961 0.98 1021 1.08 1079 1.18 1135 1.28 1188 1.38 1240 1.48
~
~
~
~
~
~
1. Blower performance includes evaporator coil and 2" filters
2. At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur. Decrease airflow downward as necessary.
SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹
0.2
0.4
0.6
0.8
1.0
1.2
Optional Hi-Static Drive + 1.5 HP
Standard Drive + 1 HP
Field Supplied Low Static 
Drive
1.4
1.6
1.8
2.0
SUPPLY AIR BLOWER PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2400
510 0.31 600 0.45 672 0.60 741 0.78 810 0.96 878 1.14 936 1.33 982 1.54 1033 1.76 1074 2.00
2800
538 0.44 628 0.57 700 0.71 778 0.89 830 1.10 890 1.29 950 1.50 1010 1.72 1048 1.92
~
~
3200
599 0.62 675 0.79 745 0.98 815 1.18 875 1.38 927 1.58 985 1.78 1037 1.99
~
~
~
~
3600
661 0.86 730 1.03 795 1.23 853 1.43 915 1.64 973 1.85
~
~
~
~
~
~
~
~
4000
712 1.10 773 1.28 830 1.50 888 1.72 946 1.95
~
~
~
~
~
~
~
~
~
~
1. Blower performance includes evaporator coil and 2" filters
2. At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur. Decrease airflow downward as necessary.
Standard Drive + 1.5 HP
Field Supplied Low Static 
Drive
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹
Optional Hi-Static Drive + 2 HP
1.4
1.6
1.8
2.0
SUPPLY
CFM
0.2
0.4
0.6
0.8
1.0
1.2
SUPPLY AIR BLOWER PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3200
599 0.62 675 0.79 745 0.98 815 1.18 875 1.38 927 1.58 984 1.78 1037 1.99 1082 2.22 1128 2.42
3600
661 0.86 730 1.03 795 1.23 853 1.43 915 1.64 973 1.85 1020 2.10 1070 2.37 1114 2.67 1160 2.89
4000
712 1.10 773 1.28 830 1.50 888 1.72 946 1.95 1004 2.19 1062 2.44 1098 2.70 1146 2.97
~
~
4400
768 1.42 824 1.62 877 1.82 930 2.04 985 2.30 1035 2.60 1085 2.90
~
~
~
~
~
~
4800
822 1.78 875 1.98 925 2.20 975 2.43 1026 2.68 1078 2.96
~
~
~
~
~
~
~
~
1. Blower performance includes evaporator coil and 2" filters
2. At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur. Decrease airflow downward as necessary.
Field Supplied Low Static 
Drive
SUPPLY
CFM
0.2
0.4
0.6
0.8
1.0
1.2
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹
Optional Hi-Static Drive + 3 HP
Standard Drive + 2 HP
1.4
1.6