Johnson Controls CSV060B-240B Manual Do Utilizador

Página de 28
FORM 145.15-IOM7 (412) 
 
 
4
 
 
JOHNSON CONTROLS 
GENERAL INFORMATION  
 
All models are shipped as factory-charged unitized 
packages. All models are designed for freestanding 
mounting on the floor, or on a field fabricated 
structural steel stand.  All  models are shipped with 
vertical evaporator fan discharge as standard.  The 
evaporator fan discharge configuration is field 
convertible on all units.  
 
The 5 ton unit utilizes a single compressor.  All 8 ~ 20 
ton models are dual compressor units with two 
independent refrigerant circuits.  All units come 
standard with a microprocessor control board (refer to 
‘Microprocessor’ section).  
 
ONLY QUALIFIED PERSONNEL SHOULD 
PERFORM INSTALLATION AND SERVICE 
OF THIS EQUIPMENT. 
 
 
 
 
 
PRE-INSTALLATION INSPECTION OF EQUIPMENT  
 
All units are factory tested to ensure safe operation 
and quality assembly. Units are packaged and sealed 
on shipping skids and shipped in first class condition. 
Torn and broken packaging, scratched or dented 
panels should be reported to carrier immediately. 
Internal inspection of all units should be performed 
prior to installation. Remove all access doors and 
check for visual defects that can occur during 
transport. Any problems found internally should be 
reported to carrier and manufacturer immediately. 
Refrigerant circuit should be checked to ensure no 
leaks have occurred during shipment. Install gauge 
set to high and low pressure ports to confirm pressure 
has been maintained and no leaks have occurred 
during shipment. Repair any damage prior to 
installation to ensure safe operation.  
 
Record any unit damage on the Bill of 
Lading and report to carrier and factory 
immediately. Shipping and handling 
damages are not warranty items.  
 
 
 
RIGGING  
 
PRIOR TO MOUNTING UNIT, CHECK 
INDIVIDUAL UNIT WEIGHTS (PAGE  10) 
AND VERIFY LIFTING CAPACITY OF 
LIFTING EQUIPMENT EXCEEDS WEIGHT 
OF UNITS BY SAFE MARGINS. FAILURE 
TO DO SO MAY RESULT IN UNIT 
DAMAGE, PERSONAL INJURY OR EVEN 
DEATH.  
 
 
To ensure safe installation of the unit when ceiling 
mount application is specified, estimate the 
approximate center of gravity of the unit. The 
configuration of internal components for each unit is 
different and weight is unevenly distributed.  
 
DETERMINE THE ACTUAL CENTER OF 
GRAVITY OF THE UNIT BY PERFORM-
ING A TEST LIFT. LIFTING AN UNBAL-
ANCED UNIT CAN CAUSE PERSONAL 
INJURY OR EVEN DEATH.  
 
 
 
 
INSTALLATION SITE  
 
LOCK ALL ELECTRICAL POWER SUP-
PLY SWITCHES IN THE OFF POSITION 
BEFORE INSTALLING THE UNIT. FAIL-
URE TO DISCONNECT POWER SUPPLY 
MAY RESULT IN ELECTRICAL SHOCK 
OR EVEN DEATH.  
 
Location  -  To ensure unit operates at maximum 
efficiencies, choose a dry indoor area where the 
temperature is controlled between 50
°F and 115°F. 
Consideration of surrounding areas should be taken 
when choosing a location to install the unit. Common 
vibration and sound levels associated with commercial 
equipment may be objectionable to people or 
equipment.  
 
Failure to allow adequate space between 
units may result in poor unit perfor-
mance and possible unit failure.  
 
 
 
 
Install thermostats, air supplies and returns so that 
each unit will operate only on individual unit control. 
To assure fast drainage of condensate run-off, unit 
can be slightly pitched in the same direction as drain 
pan outlet. 
 
CSV Operating Weight  
Unit  
Operating 
Weight (Lbs) 
Shipping 
Weight (Lbs) 
CSV060B 
590 
635 
CSV096B 
795 
835 
CSV120B 
955 
995 
CSV180B 
1310 
1365 
CSV240B 
1465 
1525