Aquacal 101 Manual Do Utilizador

Página de 214
41
Plumbing Schematic–Flow Exceeding 70-GPM
Plumbing Requirements (continued)
INSTALLATION
Plumbing Schematics – Flow 30 to 70-GPM
Bypass Check Valve
AquaCal P.N.: 2556
-or equal to-
Del Ind. PN: CO-0103
T
YPICAL
 P
OOL
 - F
LOW
 G
REATER THAN
 70-
GPM
(2-HP P
UMP OR
 L
ARGER
)
T
YPICAL
 P
OOL
 - F
LOW LESS THAN
 70-
GPM
P
OOL
/S
PILL
 O
VER
 S
PA
 - T
WO
 P
UMP
 S
YSTEM
H
EAT
 P
UMP WITH
 S
OLAR
 P
ANELS
P
OOL
/S
PILL
 O
VER
 S
PA
 - O
NE
 P
UMP
 S
YSTEM
Water flow exceeding 70-GPM may damage titanium condenser; such damage will NOT be
covered under the equipment warranty. Install a bypass check valve (AquaCal P.N.: 2556, or
equal to Del Industries P.N.: CO-0103) whenever water flow rate may exceed 70-GPM. Contact
AquaCal Technical Support (800-786-7751) for guidance regarding testing for water flow rate.
Failure to heed the following may result in damage to
equipment.
CAUTION !